Iec 61580 Goose Analog Values; Volts Per Hertz - GE T60 Instruction Manual

Ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

6 ACTUAL VALUES
Table 6–2: FLEXELEMENT™ BASE UNITS (Sheet 2 of 2)
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
SOURCE ENERGY
(SRC X Positive and Negative
Watthours); (SRC X Positive and
Negative Varhours)
SOURCE POWER
SOURCE THD & HARMONICS
SOURCE VOLTAGE

VOLTS PER HERTZ

XFMR DIFFERENTIAL CURRENT
(Xfmr Iad, Ibd, and Icd Mag)
XFMR DIFFERENTIAL
HARMONIC CONTENT
(Xfmr Harm2 Iad, Ibd, and Icd Mag)
(Xfmr Harm5 Iad, Ibd, and Icd Mag)
XFMR RESTRAINING CURRENT
(Xfmr Iar, Ibr, and Icr Mag)
PATH: ACTUAL VALUES
IEC 61850
GOOSE ANALOGS
MESSAGE
MESSAGE
The T60 Transformer Management Relay is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
ter 2 for additional details. The IEC 61850 protocol features are not available if CPU Type E is ordered.
The IEC 61850 GGIO3 analog input data points are displayed in this menu. The GGIO3 analog data values are received
via IEC 61850 GOOSE messages sent from other devices.
PATH: ACTUAL VALUES
VOLTS PER HERTZ 1
The volts per hertz actual values are displayed in this menu.
GE Multilin
Courtesy of NationalSwitchgear.com
ϕ
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
E
= 10000 MWh or MVAh, respectively
BASE
P
= maximum value of V
BASE
BASE = 100% of fundamental frequency component
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
BASE = 1.00 pu
I
= maximum primary RMS value of the +IN and -IN inputs
BASE
(CT primary for source currents, and transformer reference primary current for transformer
differential currents)
BASE = 100%
I
= maximum primary RMS value of the +IN and -IN inputs
BASE
(CT primary for source currents, and transformer reference primary current for transformer
differential currents)
METERING
IEC 61850 GOOSE ANALOGS
ANALOG INPUT
0.000
ANALOG INPUT
0.000
ANALOG INPUT 32
0.000
METERING
VOLTS PER HERTZ 1(2)
VOLTS PER HERTZ 1:
0.000 pu
T60 Transformer Management Relay
× I
for the +IN and –IN inputs
BASE
BASE

6.3.7 IEC 61580 GOOSE ANALOG VALUES

1
2
6.3 METERING
6.3.8 VOLTS PER HERTZ
6-19