Mitsubishi Electric AE-200A Instruction Book page 63

Control system/centralized controller
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

(5) IP router + Remote BBMD connection (without a connection of BBMD to the local network)
Networks can also be connected via IP routers. Broadcast messages are transmitted across networks via
remote BBMDs that are connected to other networks.
1. Sample network configuration with the use of IP routers and BBMDs
Ethernet
IP address: 192.168.2.10
*1 BMS: Building Management System
*2 Remote BBMD: Remote BACnet
2. Configuring the Network and Device Settings
The [Network and Device Settings] screen below shows the settings for the sample network configuration
with the use of IP routers above.
"Network No." is "Local". Set the Device No. and Address.
WT07921X01
IP address: 192.168.3.30
IP address: 192.168.3.1
BBMD
*2
IP
router
IP network
IP
router
BBMD
Not used
AE-200
Device ID: 21
IP address: 192.168.2.1
®
/IP Broadcast Management Device
Device ID: 32
Device ID: 31
IP address: 192.168.3.2
BACnet
BMS
*1
Device
BACnet
Device
Device ID: 22
IP address: 192.168.2.2