Mitsubishi Electric AE-200A Instruction Book page 46

Control system/centralized controller
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

8-4-4-2. Notification Address
(1) Setting "Notification Address"
Sets the notification destination device to register in the notification class ID. Select the [Notification Class ID]
for the device to set, and under [Notification Address], click [Add] to display the [Notification Address] pop-up
window.
A maximum of 5 devices can be set for each notification class ID (including broadcast).
No.
Item
Notification Address
1
Network No.
2
Device No.
3
Process Identifier
Notification Type
Unconfirmed/
4
Confirmed
WT07921X01
Sets the network number for the event notification destination
device. Here, this is fixed to "Local".
Sets the device number for the event notification destination
device. (Select from device numbers set in 8-4-2 "Network and
Device".)
Sets the process ID for the event notification destination address.
(Setting range: 0 to 4294967295)
Set to "0" unless otherwise specified.
Sets the type of the event notification to send.
Unconfirmed: Unconfirmed Event Notification
Confirmed: Confirmed Event Notification
46
Description
Default
Local
Broadcast
0
Unconfirmed