(2) Objects used for apportioned electricity billing function
Uses the apportioned electricity billing function to store electric energy apportioned by group or interlocked
unit in an accumulator object. Reads current accumulator object values for each collection cycle, and stores
this in the trend log object.
When using the apportioned electricity billing function, a "Charge" license is required for each AE-200, and
the settings for the apportioned electricity billing function using the AE-200 Initial Setting Tool is required.
Information that can be read from BACnet
calculate charges.
Accumulator objects and trend log objects are as follows.
<Accumulator object>
AC_01xx39
AC_61aa39
AC_41mm40–43
AC_410040–43
AC_01xx44
AC_61aa44
<Trend Log object>
LOG_01xx83
LOG_61aa83
LOG_41mm84–87
LOG_410084–87
LOG_01xx88
LOG_61aa88
* xx: Group number (01–50)
* mm: PI controller address (01–50), Pulse Input (00)
* aa: Interlocked unit address (01–50)
*1 "Group Apportioned Electric Energy" and "Group Apportionment Parameter" cannot be used at the same time. If you try to check the
check boxes of both objects, then one of the check boxes will be automatically deselected.
*2 "Interlocked Units Apportioned Electric Energy" and "Interlocked Units Apportionment Parameter" cannot be used at the same time. If
both are selected, then one of the check boxes will be automatically deselected.
*3 "Pulse Input Electric Energy" settings are common to "PI controller Electric Energy". When using "Pulse Input Electric Energy 1–4",
select the check box of the "PI controller Electric Energy 1–4" object.
*4 If selecting the Trend Log object check box, the collection target accumulator object check box will also be automatically selected.
*5 When using an apportioned electricity billing function, a built-in Pulse Input (PI) of AE-200 cannot be used.
*6 Objects for the OA Processing units that are interlocked with indoor units
WT07921X01
Object name
Group Apportioned Electric
Energy
*1
Interlocked Units
Apportioned Electric Energy
*2*6
PI controller Electric Energy
1–4
*3
Pulse Input Electric Energy
1–4
*3
Group Apportionment
Parameter
*1
Interlocked Units
Apportionment Parameter
*2*6
*4
Trend Log Group
Apportioned Electric Energy
Trend Log Interlocked Units
Apportioned Electric Energy
Trend Log PI controller
Electric Energy 1–4
Trend Log Pulse Input
Electric Energy 1–4
Trend Log Group
Apportionment parameter
Trend Log Interlocked Units
Apportionment Parameter
®
is electric energy or apportionment parameters, and this does not
Stores cumulative value of electric energy for each group.
Stores cumulative value of electric energy for each interocked unit.
Stores cumulative value (4 channels) of electric energy
accumulated with the PI controller.
Stores cumulative value (4 channels) of electric energy
accumulated with the AE-50/EW-50 built-in Pulse Input (PI).
Stores cumulative value of electric energy apportionment parameter
for each group.
Stores cumulative value of electric energy apportionment parameter
for each interlocked unit.
Accumulates the accumulator (AC_01xx39) "Present_Value" for
each collection cycle (Log_Interval property).
Accumulates the accumulator (AC_61aa39) "Present_Value" for
each collection cycle (Log_Interval property).
Accumulates the accumulator (AC_41mm40–43) "Present_Value"
for each collection cycle (Log_Interval property).
Accumulates the accumulator (AC_410040–43) "Present_Value"
for each collection cycle (Log_Interval property).
Accumulates the accumulator (AC_01xx44) "Present_Value" for
each collection cycle (Log_Interval property).
Accumulates the accumulator (AC_61aa44) "Present_Value" for
each collection cycle (Log_Interval property).