Quick guide for selecting between gG and aR fuses

The table below is a short cut in selecting between gG and aR fuses. The
combinations (cable size, cable length, transformer size and fuse type) in the table
fulfil the minimum requirements for the proper operation of the fuse.
ACS800-01 size
Copper
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0025-2
3×25 Cu
-0030-2
3×35 Cu
-0040-2
3×50 Cu
-0050-2
3×70 Cu
-0060-2
3×95 Cu
-0070-2
3×120 Cu
Three-phase supply voltage 380 V, 400 V or 415 V
-0040-3
3×25 Cu
-0050-3
3×35 Cu
-0060-3
3×50 Cu
-0075-3
3×70 Cu
-0070-3
3×70 Cu
-0100-3
3×95 Cu
-0120-3
3×120 Cu
-0135-3
3×150 Cu
-0165-3
3×185 Cu
-0205-3
3×240 Cu
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0050-5
3×25 Cu
-0060-5
3×25 Cu
-0070-5
3×35 Cu
-0105-5
3×70 Cu
-0100-5
3×70 Cu
-0120-5
3×95 Cu
-0140-5
3×95 Cu
-0165-5
3×150 Cu
-0205-5
3×185 Cu
-0255-5
3×240 Cu
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0050-7
3×16 Cu
-0060-7
3×16 Cu
-0070-7
3×25 Cu
-0100-7
3×35 Cu
-0120-7
3×50 Cu
-0145-7
3×70 Cu
-0175-7
3×95 Cu
-0205-7
3×95 Cu
Note 1: The supply transformer minimum power in kVA is calculated with a z
frequency 50 Hz.
Note 2: The table is not intended for transformer selection - that must be done separately.
Cable type
Aluminium
Maximum cable length with gG
10 m
3×35 Al
3×50 Al
3×70 Al
3×95 Al
3×120 Al
3×185 Al
3×35 Al
3×50 Al
3×70 Al
100
3×95 Al
130
3×95 Al
130
3×120 Al
150
3×185 Al
170
3×240 Al
200
3×240 Al
240
2×(3×95) Al
232
3×35 Al
3×50 Al
3×70 Al
130
3×95 Al
160
3×95 Al
160
3×120 Al
190
3×150 Al
190
3×240 Al
250
3×240 Al
290
2×(3×95) Al
289
3×25 Al
3×25 Al
3×50 Al
3×50 Al
130
3×70 Al
180
3×95 Al
220
3×120 Al
260
3×150 Al
340
Supply transformer minimum apparent power S
fuses
50 m
100 m
31
38
44
55
58
71
72
87
85
110
99
120
54
57
71
76
82
110
110
140
140
160
140
160
160
190
190
210
220
250
260
310
257
310
67
70
79
95
110
130
140
160
170
190
170
190
200
220
200
220
260
290
320
360
312
355
65
67
70
70
70
70
95
95
99
140
150
180
190
220
240
260
280
360
390
Maximum cable length with aR
fuses
10 m
100 m
-
27
27
-
33
33
-
41
41
-
55
70
-
65
70
-
81
81
48
48
58
58
70
70
99
99
96
96
120
120
140
140
160
160
180
180
134
153
56
56
68
68
83
83
130
130
110
120
140
140
160
160
200
200
230
230
167
185
63
63
70
70
95
95
110
110
140
140
160
160
200
200
230
230
value of 6% and
k
99
(kVA)
N
200 m
-
-
-
-
-
-
48
58
70
140
140
140
140
160
200
196
56
68
83
150
150
150
160
200
230
218
63
70
95
110
140
160
200
230
Technical data