Symbols; Sizing - ABB ACS800 Hardware Manual

Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

ACS800-01 size
Nominal
ratings
I
cont.max
A
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0011-7
13
-0016-7
17
-0020-7
22
-0025-7
25
-0030-7
33
-0040-7
36
-0050-7
51
-0060-7
57
-0070-7
79
-0100-7
93
-0120-7
113
-0145-7
134
-0175-7
166
-0205-7
190

Symbols

Nominal ratings
I
cont.max
I
max
Typical ratings:
No-overload use
P
cont.max
Light-overload use (10% overload capability)
I
2N
P
N
Heavy-duty use (50 % overload capability)
I
2hd
P
hd

Sizing

The current ratings are the same regardless of the supply voltage within one voltage range. To achieve
the rated motor power given in the table, the rated current of the drive must be higher than or equal to
the rated motor current.
Note 1: The maximum allowed motor shaft power is limited to 1.5 · P
value is greatest). If the limit is exceeded, motor torque and current are automatically restricted. The
function protects the input bridge of the drive against overload. If the condition exists for 5 minutes, the
limit is set to P
Note 2: The ratings apply at an ambient temperature of 40 °C (104 °F). At lower temperatures the
ratings are higher (except I
Note 3: Use the DriveSize PC tool for a more accurate dimensioning if the ambient temperature is
below 40 °C (104 °F) or the drive is loaded cyclically.
Light-overload
No-
overload
use
use
I
P
I
cont.max
max
2N
kW
A
A
14
11
11.5
19
15
15
28
18.5
20
38
22
23
44
30
30
54
30
34
68
45
46
84
55
52
104
75
73
124
90
86
172
110
108
190
132
125
245
160
155
245
160
180
continuous rms output current. No overload capability at 40 °C.
maximum output current. Available for 10 s at start, otherwise as long as allowed by drive
temperature.
typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,
230 V, 400 V, 500 V or 690 V.
continuous rms current. 10% overload is allowed for one minute every 5 minutes.
typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,
230 V, 400 V, 500 V or 690 V.
continuous rms current. 50% overload is allowed for one minute every 5 minutes.
typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,
230 V, 400 V, 500 V or 690 V.
.
cont.max
).
max
Heavy-duty use
P
I
P
N
2hd
kW
A
kW
7.5
8.5
5.5
11
11
7.5
15
15
11
18.5
19
15
22
22
18.5
30
27
22
37
34
30
45
42
37
55
54
45
75
62
55
90
86
75
110
95
90
132
131
110
160
147
132
Frame
Air flow
size
hd
3
m
/h
R4
103
R4
103
R4
103
R4
103
R4
103
R4
103
R5
250
R5
250
R6
405
R6
405
R6
405
R6
405
R6
405
R6
405
PDM code: 00096931-J
, 1.1 · P
or P
hd
N
cont.max
Technical data
91
Heat
dissipation
W
300
340
440
530
610
690
840
1010
1220
1650
1960
2660
3470
4180