ABB ACS800 Hardware Manual page 98

Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

98
ACS800-01 size
Input
current
-0060-7
58
-0070-7
79
-0100-7
91
-0120-7
112
-0145-7
131
-0175-7
162
-0205-7
186
1)
minimum short-circuit current of the installation
Note 1: See also Planning the electrical installation:
For UL recognized fuses, see
Note 2: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Larger fuses than the recommended ones must not be used.
Note 4: Fuses from other manufacturers can be used if they meet the ratings and the melting curve of
the fuse does not exceed the melting curve of the fuse mentioned in the table.
Technical data
Ultrarapid (aR) fuses
Min.
short-
circuit
1)
current
A
A
A
400
100
4650
520
125
8500
695
160
16000
750
200
15000
1520
350
68500
1520
350
68500
1610
400
74000
NEMA data
Fuse
2
s
V
Manufacturer
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
Thermal overload and short-circuit
on page 102.
Type
IEC size
170M1567
000
170M1568
000
170M1569
000
170M3815
1*
170M3818
DIN1*
170M3818
DIN1*
170M5808
DIN2*
protection.
PDM code: 00096931-J, 00556489