Setting Groups - GE b30 Instruction Manual

Bus differential system
Hide thumbs Also See for b30:
Table of Contents

Advertisement

CONTROL ELEMENTS

5.8.3 Setting groups

5
SETTINGS  CONTROL ELEMENTS  SETTING GROUPS
 SETTING GROUPS
The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the
settings menu. The active setting group can be indicated on the front display of the UR by configuring User-
ELEMENTS
Programmable LEDs to display the state of the
SETTING GROUPS FUNCTION
activated. The default setting group is forced active while the
SETTING GROUPS BLK —
can be useful in applications where it is undesirable to change the settings under certain conditions, such as during a
control sequence.
5-206
Figure 5-108: Trip bus logic
SETTING GROUPS
FUNCTION: Enabled
SETTING GROUPS BLK:
Off
GROUP 2 ACTIVATE ON:
Off
GROUP 6 ACTIVATE ON:
Off
GROUP 1 NAME:
GROUP 6 NAME:
SETTING GROUP
EVENTS: Disabled
SETTING GROUP ACT
— When Enabled, allows setting groups other than group 1 (the default active group) to be
Prevents the active setting group from changing when the selected FlexLogic operand is "On." This
Range: Disabled, Enabled
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: up to 16 alphanumeric characters
Range: up to 16 alphanumeric characters
Range: Disabled, Enabled
FlexLogic operands.
SETTING GROUPS FUNCTION
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
GROUPED
setting is Disabled.