Section 6 Diagnostics and Troubleshooting
1.
2.
Tags not Created in Redundant 800xA History Embedded
Data Collector Node
From the 800xA History server try to connect the Redundant 800xA History
Embedded Data Collector Node using Vtrin GUI:
If the connection fails, then check the 800xA History Embedded Data Collector
Node services in redundant node are running.
Open vtrin Interface in Main Server, browse to Maintenance > Basic > Database
Nodes. Check the redundant 800xA History Embedded Data Collector Node is
listed. If not run the Scheduler service from Service Management in Redundant
800xA History Embedded Data Collector Node and Primary 800xA History
Embedded Data Collector Node .
Once the redundant 800xA History Embedded Data Collector Node is listed, check
for the created tag.

Trends not appearing in some client nodes

1.
2PAA107563-600 B
The 800xA HistorySync Service for Redundant 800xA History Embedded
Data Collector Node should be standby mode.
When a log is created, the tags will be first created in Primary 800xA History
Embedded Data Collector Node then to 800xA History Server and then will be
created in secondary 800xA History Embedded Data Collector Node (by
800xA History Server).
Connection String: tcp://Redundant 800xA History Embedded Data Collector
Node IP:7614/CPIMS-INTERNAL/"800xA History Embedded Data Collector
Node Computer Name"-RTDB,
Username: User Account used for 800xA History Embedded Data Collector
Node Installation
Password: User Account used for 800xA History Embedded Data Collector
Node Installation.
Right-click the PPA SystemTray Icon and select Service Connection Viewer.
Tags not Created in Redundant 800xA History