SECTION 4. HEGS5BLX CONFIGURATION

4.1

SYSTEM PARAMETERS

The address of the controller and baud rate are configurable.
1. Power down the unit and power it back up.
2. Press the middle soft key below the LCD after the controller counts down, while the
application screen is being displayed as shown below.
3. Press Enter to accept the current address shown in parenthesis or enter a new
address using the numeric keys and press Enter. The Tilt configuration is displayed.
4. Press 1 for normal tilt operation. Press 2 to reverse the tilt operation; that is the tilt
up command sends a tilt down command to the PTZ and the tilt down command
sends a tilt up command to the PTZ. When the desired selection is displayed, press
Enter. The baud rate configuration is displayed.
5. Press the + and – keys to scroll through the available baud rates, 1200, 9600,
19200, and 57600. When the desired baud rate is displayed, press Enter. The
default baud rate is 19200. The controller returns to the Login screen.
Rev. 1.01
HEGS5BLX
030106
922.0255 Rev.A
Address (1):
1
Stick Dir:
Norm
1: Norm
2:Rev
Baud Rate:
19200
(+/-)
Please Login
Login
F1
13
900.0799
20-Jun-06