CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS

Parameter Setting

Parameter
Description
setting
P10-00=2
Choose Fixed quantity circulation with PID
P10-01=X
Number of Motors: Maximum 4 motors. After setting number of motor to be connected at the
same time, multi-function output terminals will follow automatically the setting as shown in the
table below.
P10-01 01
P02-13 55
P02-14
P02-15
P02-34
P02-35
P02-36
P02-37
P02-38
P10-03=X
Delay Time due to the Acceleration (or the Increment) at Motor Switching (unit: second)
P10-04=X
Delay Time due to the Deceleration (or the Decrement) at Motor Switching (unit: sec)
P10-05=X
Delay time while fixed quantity circulation at Motor Switching with PID (unit: seconds)
P10-06=X
Frequency when switching motors at fixed quantity circulation (Hz)
Disable Motor Output
Set the Multifunction Input Commands as Disable Motors' Output can stop corresponding motors. The settings are:
P02-01~P02-06=
Disable Motor Output
When a motor's output is disabled, this motor will park freely.
Fixed quantity circulation with PID can control up to 4 motors.
The diagram below is an example of controlling 4 motors.
63-4528—04
02
03
04
55
55
55
56
546
56
57
57
58
Table 2: Setting of Multi-function Output Terminal on Circulating Motors
60
61
ALL
1
05
06
07
08
55
55
55
55
56
56
56
56
57
57
57
57
58
58
58
58
59
59
59
59
60
60
60
61
61
62
62
63
64
65
66
2
3
4
5
6
234
Motor #1 by Mains
Motor #2 by Mains
Motor #3 by Mains
Motor #4 by Mains
Motor #5 by Mains
Motor #6 by Mains
Motor #7 by Mains
Motor #8 by Mains
67
68
7
8