CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
• It is for digital input terminal signal delay and confirmation. The delay time is confirmation time to prevent some uncertain
interference that would cause error in the input of the digital terminals. Under this condition, confirmation for this parameter
would improve effectively, but the response time will be somewhat delayed.
02 - 12
Multi-function Input Mode Selection
Settings
• The setting of this parameter is in hexadecimal.
• This parameter is to set the input signal level and it won't be affected by the SINK/SOURCE status.
• Bit0 is for FWD terminal, bit1 is for REV terminal and bit2 to bit15 is for MI1 to MI14.
• User can change terminal status by communicating.
For example, MI1 is set to 1 (multi-step speed command 1), MI2 is set to 2 (multi-step speed command 2). Then the forward +
nd
2
step speed command=1001(binary)= 9 (Decimal). Only need to set Pr.02-12=9 by communication and it can forward with
nd
2
step speed. It doesn't need to wire any multi-function terminal.
Bit15
bit14
bit13
bit12
MI14
MI13
MI12
MI11
02 - 13
Relay1: Multi Output Terminal
02 - 14
Relay2: Multi Output Terminal
02 - 15
Relay3: Multi Output Terminal
02 - 16
Multi-output Direction
Settings
• The setting of this parameter is in hexadecimal.
• This parameter is set via bit setting. If a bit is 1, the corresponding output acts in the opposite way. For example: If Pr02-13=1,
Relay 1 is open when the drive runs and is closed when the drive is stopped
Bit15
bit14
bit13
bit12
MO20 MO19 MO18 MO17 MO16 MO15 MO14 MO13 MO12 MO11 MO10 MO2
02 - 17
Terminal count value attained (returns to 0)
Settings
• The counter trigger can be set by the multi-function terminal MI6 (set Pr.02-06 to 23). Upon completion of counting, the
specified output terminal will be activated (Pr.02-13~02-14, Pr.02-34, 02-35 is set to 18). Pr.02-17 can't be set to 0.
• When the display shows c5555, the drive has counted 5,555 times. If display shows c5555l it means that real counter value is
between 55,550 to 55,559.
63-4528—04
0~65535 (0:N.O.; 1:N.C.)
bit11
bit10
bit9
bit8
MI10
MI9
MI8
MI7
0~65535 (0:N.O.; 1:N.C.)
bit11
bit10
bit9
bit8
0~65500
bit7
bit6
bit5
bit4
MI6
MI5
MI4
MI3
bit7
bit6
bit5
bit4
144
Factory Setting: 0
bit3
bit2
bit1
bit0
MI2
MI1
REV
FWD
Factory Setting: 11
Factory Setting: 1
Factory Setting: 9
Factory Setting: 0
bit3
bit2
bit1
bit0
MO1
??
RY2
RY1
Factory Setting: 0