06 - 22
Fault Output Option 1
06 - 23
Fault Output Option 2
06 - 24
Fault Output Option 3
06 - 25
Fault Output Option 4
Settings
• These parameters can be used with multi-function output (set to 35-38) for the specific requirement. When the fault occurs, the
corresponding terminals will be activated (It needs to convert binary value to decimal value to fill in Pr.06-22 to Pr.06-25)
Fault Code
0: No fault
1: Over-current during acceleration (ocA)
2: Over-current during deceleration (ocd)
3: Over-current during constant speed (ocn)
4: Ground fault (GFF)
5: IGBT short-circuit (occ)
6: Over-current at stop (ocS)
7: Over-voltage during acceleration (ovA)
8: Over-voltage during deceleration (ovd)
9: Over-voltage during constant speed (ovn)
10: Over-voltage at stop (ovS)
11: Low-voltage during acceleration (LvA)
12: Low-voltage during deceleration (Lvd)
13: Low-voltage during constant speed (Lvn)
14: Stop mid-low voltage (LvS)
15: Phase loss protection (OrP)
16: IGBT over-heat (oH1)
17: Capacitance over-heat (oH2)
18: tH1o (TH1 open)
19: tH2o (TH2 open)
20: Reserved
21: Drive over-load (oL)
22: Electronics thermal relay 1 (EoL1)
23: Electronics thermal relay 2 (EoL2)
24: Motor PTC overheat (oH3) (PTC)
25: Reserved
26: Over-torque 1 (ot1)
27: Over-torque 2 (ot2)
28: Low current (uC)
29: Reserved
30: Memory write-in error (cF1)
0 to 65535 sec (refer to bit table for fault code)
Bit0
current
CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
Bit1
Bit2
Volt.
OL
183
Factory Setting: 0
Bit3
Bit4
Bit5
SYS
FBK
EXI
Bit6
CE
63-4528—04