CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
03 - 04
Analog Input Bias 1 (ACI)
Settings
• It is used to set the corresponding ACI voltage of the external analog input 0.
03 - 05
AVI2 Analog Positive Input Bias
Settings
• It is used to set the corresponding AVI2 voltage of the external analog input 0.
• The relation between external input voltage/current and setting frequency: 0~10V (4-20mA) corresponds to 0-60Hz.
03 - 06
Positive/negative Bias Mode (AVI1)
03 - 07
Positive/negative Bias Mode (ACI)
03 - 08
Positive/negative Bias Mode (AVI2)
Settings
• In a noisy environment, it is advantageous to use negative bias to provide a noise margin. It is recommended NOT to use less
than 1V to set the operation frequency.
63-4528—04
-100.0~100.0%
-100.0~100.0%
0: Zero bias
1: Lower than bias=bias
2: Greater than bias=bias
3: The absolute value of the bias voltage while serving as the center
4: Serve bias as the center
03-00 TO 03-02
-10V -9 -8 -7 -6 -5 -4 -3 -2 -1
1 2 3 4 5 6 7 8 9
NEGATIVE
BIAS
POSITIVE
BIAS
10V
03 -11 ~ 03 -1 4 GAIN IS POSITIVE
0 ZERO BIAS
BIAS
1 LOWER THAN BIAS BIAS
BIAS
2 GREATER THAN BIAS BIAS
3 THE ABSOLUTE VALUE OF
THE BIAS VOLTAGE WHILE
SERVING AS THE CENTER
4 SERVE BIAS AS THE CENTER
M33660