Honeywell VFD CORE Installation Instructions Manual page 99

User and application manual
Hide thumbs Also See for VFD CORE:
Table of Contents

Advertisement

Parameter
00-12
Carrier Frequency (KHz)
PLC command mask (SOOC,
00-13
SOOF)
Source of the MASTER
00-14
Frequency Command (AUTO)
Source of the Opertaion
00-15
Command (AUTO)
00-16
Stop method
Motor Operating Direction
00-17
Control
Memory of Communication
00-18
Frequency Command
00-19
User Defined Property
00-20
Max. User Defined Value
Function
2~15kHz
2~10kHz
2~9kHz
0~65535
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
6: CANopen communication card
8: Communication card (no CANopen card)
0: Digital keypad
1: External analog input (Pr.03-00)
2: RS-485 serial communication
3: External UP/DOWN terminal
5: Communication card ( not included CANopen card)
0: Ramp to stop
1: Coast to stop
0: Enable forward/reverse
1: Reverse disable
2: Forward disable
Read Only
Bit 0~3: user defined on decimal places
0000b: no decimal place
0001b: one decimal place
0010b: two decimal place
0011b: three decimal place
Bit 4~15: user define on unit
000xh: Hz
001xh: rpm
002xh: %
003xh:kg
0: Disable
0000b: 0~65535 (No decimal place in Pr.00-19 setting)
0001b: 0.0~6553.5 (One decimal place in Pr.00-19
0010b: 0.0~655.35(Two decimal place in Pr.00-19 setting)
0011b: 0.0~65.536 (Three decimal place in Pr.00-19
setting)
CHAPTER 11: SUMMARIES OF PARAMETER SETTINGS
Setting
230V
460V
230V
460V
230V
460V
setting)
99
Factory
Setting
Normal duty:
1~20hp
Heavy duty:
0.5~15HP
8
Normal duty:
1~25hp
Heavy duty:
0.5~20HP
Normal duty:
25~60hp
Heavy duty:
20~50hp
6
Normal duty:
30~100hp
Heavy duty:
25~75hp
Normal duty:
75~125hp
Heavy duty:
60~100hp
4
Normal duty:
125~536hp
Heavy duty:
100~475hp
0
Read
Only
2
1
1
1
Read
Only
0
0
63-4528—04