Chapter 4. WIRING
3-wire system RS-485 mutual connection
Handling Precautions
Be sure to connect SG terminals each
others.
Failure to do so might cause unstable
communications.
Provide terminating resistor of 150
Grounding of the shielded FG terminal should be carried out at only one end and not both ends.
When there are only three RS-485 terminals, terminals marked * are wired internally.
4-18
Terminating resistor
Master station
RDA
RDB
*
SDA
*
SDB
SG
FG
Shielded cable
Shielded cable
Terminating resistor
5%, 1/2W min. at both ends of the communications path.