Honeywell DCP301 User Manual page 117

Digital program controller
Table of Contents

Advertisement

Chapter 7. PARAMETER SETUP
No.
Item Code
C 8 2
82
Expansion setting 2
C 8 3
83
Unused
C 8 4
84
Station address
C 8 5
85
Transmission rate/
character format
C 8 6
86
Unused
C 8 7
87
Unused
C 8 8
88
Unused
C 8 q
89
Unused
C q 0
90
Special functions
C q 1
91
Input 1 zener barrier
adjustment
C q 2
Unused
92
C q 3
93
CPL communica-
tions port selection
C q 4
94
PID type
C q 5
95
Unused
C q 6
96
Hardware type 1
C q 7
97
Hardware type 2
C q 8
98
ROM ID
C q q
99
ROM item
C 0 0
100
ROM revision
7-32
Item
Factory
User
Setting
Setting
0
0
0
0
0
0
Setting
0: Expansion disabled
1: Expansion enabled
[Note]
This setting is for service use only.
[Note]
"– – – –" is displayed and setting is not possible.
0 to 127
[Note]
On models not supporting communications, "– – – –" is
displayed and setting is not possible.
0 disables communication.
0: 9600bps/even parity, 1 stop bit
1: 9600bps/no parity, 2 stop bits
2: 4800bps/even parity, 1 stop bit
3: 4800bps/no parity, 2 stop bits
[Note]
On models not supporting communications, "– – – –" is
displayed and setting is not possible.
[Note]
"– – – –" is displayed and setting is not possible.
[Note]
Normally set to "0".
[Note]
"– – – –" is displayed and setting is not possible.
[Note]
"– – – –" is displayed and setting is not possible.
0:
Add-on terminal
1 to 15: Loader jack (communications address)
0: Improved
1: Compatible with DCP200
[Note]
"– – – –" is displayed and setting is not possible.
[Note]
This setting is for service use only, and can only be
verified.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents