Chapter 11. CALIBRATION
Cold junction sensor calibration
The cold junction input 0%
The cold junction AD count data
The cold junction temperature data
Current output calibration
OUT CH1 output calibration
OUT CH2 output calibration
OUT CH1 output calibration
11-12
keys to show (
Scroll , ,
, or
key.
(1) Press SETUP key until the PROG/SEG display shows (
(2) Press ENT key after display stabilizes, AD count is shown on lower display.
(1) Press SETUP key until the PROG/SEG display shows (
(2) Press ENT key after display stabilizes, AD count is shown on lower display.
(1) Press SETUP key until the PROG/SEG display shows (
(2) Connect the thermometer (55).
(3) Scroll , ,
, or
(4) Press ENT key.
Scroll , ,
, or
keys to show (
key.
Connect the digital ammeter across terminals (See Figure 11-9).
(1) Press PARA key until the PROG/SEG display shows (
Scroll , ,
, or
(2) Press PARA key until the PROG/SEG display shows (
Scroll , ,
, or
(1) Press PARA key until the PROG/SEG display shows (
Scroll , ,
, or
(2) Press PARA key until the PROG/SEG display shows (
Scroll , ,
, or
(1) Press PARA key until the PROG/SEG display shows (
Scroll , ,
, or
(2) Press PARA key until the PROG/SEG display shows (
Scroll , ,
, or
2.0.2.2.
keys to set above temperature value(°C).
4.0.4.4.
) on the upper display, then press ENT
keys until meter indicates 4.00mA, then press ENT key.
keys until meter indicates 20.00mA, then press ENT key.
keys until meter indicates 4.00mA, then press ENT key.
keys until meter indicates 20.00mA, then press ENT key.
keys until meter indicates 4.00mA, then press ENT key.
keys until meter indicates 20.00mA, then press ENT key.
) on upper display, then press ENT
02-01
).
02-02
).
02-03
).
04-01
).
04-02
).
06-03
).
06-04
).
04-05
).
04-06
).