Installation Precautions - Honeywell HW-AV-LTE-M Installation And Operation Manual

Clss pathway
Hide thumbs Also See for HW-AV-LTE-M:
Table of Contents

Advertisement

Honeywell Connected Life Safety Services | Honeywell Connected Life Safety Services

INSTALLATION PRECAUTIONS

ADHERENCE TO THE FOLLOWING WILL AID IN
PROBLEM-FREE INSTALLATION WITH LONG-
TERM RELIABILITY:
WARNING - Several different sources of power can be connected
to the fire alarm control panel. Disconnect all sources of power
before servicing. Control unit and associated equipment may be
damaged by removing and/or inserting cards, modules, or
interconnecting cables while the unit is energized. Do not attempt
to install, service, or operate this unit until manuals are read and
understood.
CAUTION - System Re-acceptance Test after Software Changes:
To ensure proper system operation, this product must be tested in
accordance with NFPA 72 after any programming operation or
change in site-specific software. Re-acceptance testing is required
after any change, addition or deletion of system components, or
after any modification, repair or adjustment to system hardware or
wiring. All components, circuits, system operations, or software
functions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly
affected by the change, up to a maximum of 50 devices, must also
be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º
C/32-120º F and at a relative humidity 93% ± 2% RH (non-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of
the system's standby batteries and the electronic components may
be adversely affected by extreme temperature ranges and humidity.
Therefore, it is recommended that this system and its peripherals be
installed in an environment with a normal room temperature of 15-
27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indicating
device loops. Most devices cannot tolerate more than a 10% I.R.
drop from the specified device voltage.
Like all solid state electronic devices, this system may operate
erratically or can be damaged when subjected to lightning induced
transients. Although no system is completely immune from
lightning transients and interference, proper grounding will reduce
FCC  REQUIREMENTS
Warning:  This equipment generates, uses, and can radiate radio
frequency energy and if not installed and used in accordance with
the instruction manual may cause interference to radio
communications. It has been tested and found to comply with the
limits for Class A computing devices pursuant to Subpart B of Part
15 of FCC Rules, which is designed to provide reasonable protection
against such interference when devices are operated in a
commercial environment. Operation of this equipment in a
residential area is likely to cause interference, in which case the user
will be required to correct the interference at his or her own expense.
©2024 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Installation and Operation Manual | REV. B
susceptibility. Overhead or outside aerial wiring is not
recommended, due to an increased susceptibility to nearby
lightning strikes. Consult with the Technical Services Department if
any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting
circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make all
cable entries from the sides or rear. Before making modifications,
verify that they will not interfere with battery, transformer, or printed
circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening
may damage threads, resulting in reduced terminal contact
pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground
yourself with a proper wrist strap before handling any circuits so
that static charges are removed from the body. Usestatic
suppressive packaging to protect electronic assemblies removed
from the unit.
Units with a touchscreen display should be cleaned with a dry,
clean, lint free/microfiber cloth. If additional cleaning is required,
apply a small amount of Isopropyl alcohol to the cloth and wipe
clean. Do not use detergents, solvents, or water for cleaning. Do not
spray liquid directly onto the display.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment. FACP
operation and reliability depend upon proper installation.
 
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and
Acclimate® Plus™, FlashScan®, FAAST Fire Alarm Aspiration
Sensing Technology®, Honeywell®, INSPIRE®, Intelligent FAAST®,
NOTIFIER®, ONYX®, ONYXWorks®, SWIFT®, VeriFire®, a are all
registered trademarks of Honeywell International Inc. Microsoft®
and Windows® are registered trademarks of the Microsoft
Corporation. Chrome™ and Google™ are trademarks of Google Inc.
Firefox® is a registered trademark of The Mozilla Foundation.
 
Canadian Requirements
This digital apparatus does not exceed the
Class A limits for radiation noise emissions
from digital apparatus set out in the Radio
Interference Regulations of the Canadian
Department of Communications.
Le present appareil numerique n'emet pas de
bruits radioelectriques depassant les limites
applicables aux appareils numeriques de la
classe A prescrites dans le Reglement sur le
brouillage radioelectrique edicte par le
ministere des Communications du Canada
ii
Wednesday, February 28, 2024

Advertisement

Table of Contents
loading

Table of Contents