Table 5 - Advanced Configuration parameters, cont'd
Key:
Plain = Read only
Latching Mode
Distance Offset
Simulation
Status
Loop Current
Simulation
Distance
Simulation
Write Protect
Write Protect
On/Off
D/A trim
Loop test
Master Reset
Factory Reset
Lock dev status
Lock/Unlock
Device
Summary
Page 18
Bold = Configurable
Bold underline = Method
Services
When enabled, causes all critical sensor failures to latch to the Critical
Fault state. The fault may only be cleared by device reset. When disabled,
the critical sensor input failure will be cleared if the input recovers.
Enable/disable can be achieved by selecting Yes/No against this
parameter.
This parameter is used to adjust the measured Distance reported by
transmitter. This parameter should be used to nullify the difference
between the actual distance (hand-dipped or other reference meter
reading) and measured distance value from the transmitter. This is a
polarity sensitive parameter and based on -/+ value the measured
Distance will be adjusted
This parameter with show the ON/OFF state of simulation
This parameter will set the Loop Current to the value entered by user
This parameter will set the Distance variable value to the value entered
by user
Displays the current configuration of the write protect function. Write
Protect is "Enabled" if either the write protect jumper on the electronics
board is in the "ON" position or the firmware write protect has been
enabled.
The write protect jumper must be set in the Enabled position for SIL
safety applications.
Configure the firmware write protect option.
Write Protect selections are:
Enable: Enables the firmware write protect option (changes in
configuration parameters will not be permitted).
Disable: Disables the firmware write protect option (requires a
password).
A 6-digit password is required to change the Write Protect option from
"Enabled" to "Disabled" to allow configuration changes. The default
password is "000000", and can be re-configured by the user.
Note: This cannot be changed if transmitter's Write Protect hardware
jumper is disabled. See the SLN700 SmartLine NCR Transmitter User's
Manual, Document #34-SL-25-13 for details.
Defined in section
Used to perform the loop test.
Choose 4 mA and 20 mA analog output levels and fix the field device
outputs at 4 mA and 20 mA
Selecting this option will cause a Master Reset of the transmitter, which is
the equivalent to power cycling the device.
Resets all device configuration parameters to their factory defaults and
triggers a soft reset. The User will be prompted to confirm they want to
take this action.
Select the Lock state for access by HART
If "Yes" is selected to lock the device, also select "Yes" or "No" to choose
whether the lock is "permanent." If the lock is not permanent, it will be
cleared on power cycle or Master Reset of the device.
If "Yes" is selected to unlock the device, the lock state will be cleared.
Summary
Shows the important advanced configuration parameters.
SLN700 Series HART
Bold italic = Table or graph
4.3.1
configuration tools.
Option User's Manual
Revision 1