Honeywell HercuLink User Manual page 28

Table of Contents

Advertisement

HercuLink
Calibration
Step
7
Click the Function button to access the Calibration Complete state. If the next state can not be
achieved, then the POS output is not calibrated correctly.
8
Click the Close button to exit the NCS Calibration procedure. This will return you to the Home
page.
ATTENTION: After you click Close button the unit will remain in MAN mode, whether or not you
clicked the Function button. To change to AUTO mode, go to Main menu, Configuration,
Lockout, then select MODE CHG.
20
Action
HercuLink™ - User Manual
Release 3
8/02