Honeywell HercuLink User Manual page 20

Table of Contents

Advertisement

HercuLink
Calibration
Step
4
Click the Function button to access the Begin Calibration state.
5
Click the Function button to access the Apply Motor Lo Calibration state.
The motor can be positioned to its low limit by using the Decr - 10% as a coarse adjust. Click it
several times to get close to the actual position desired. Then click the Decrement button to
fine-tune the final low calibration point. The motor can also be positioned with the optional
auto/manual switch on the side of the unit, or with the optional handwheel.
Note: If at any time question marks (?) are observed in both the upper and lower
displays, this is an indication that communications between the PDA and the unit have
been lost. To check communications, see Preparation on page 1.
12
Action
HercuLink™ - User Manual
Release 3
8/02