Toshiba VFNC3-2001P Instruction Manual page 43

Industrial inverter
Table of Contents

Advertisement

efesotomasyon.com -Toshiba inverter,drive,servo,plc
Terminal
Input /
symbol
output
OUT
Output
NO
2
FLA
FLB
Output
FLC
Function
Multifunction programmable open
collector output. Standard default settings
detect and output low speed signal.
Multifunction output terminals to which
two different functions can be assigned.
The NO terminal is an isoelectric output
terminal. It is insulated from the CC
terminal.
By changing parameter settings, these
terminals can also be used as
multifunction programmable pulse train
output terminals.
Multifunction programmable relay contact
output.
Detects the operation of the inverter's
protection function.
Contact across FLA-FLC is closed and FLB-
FLC is opened during protection function
operation.
Electrical
specifications
Open collector output
24Vdc-100mA
To output pulse
OUT
trains,
a current of 10mA
or more needs to
be passed.
Pulse frequency
range:
38~1600Hz
250Vac-2A
(cosφ=1)
: at resistance
load
30Vdc-1A
250Vac-1A
(cosφ=0.4)
B-8
E6581595
Inverter internal circuits
10
NO
+24V
FLA
FLB
RY
FLC