4) Use a general purpose squirrel-cage motor with a capacity that is the same as the inverter's rated capacity or
one rank below.
The minimum applicable motor capacity is 0.05kW.
5) Use a motor that has 2-8 P.
6) Always operate the motor in single operation (one inverter to one motor). Sensorless vector control
cannot be used when one inverter is operated with more than one motor.
When using a combination of several motors, set the V/F constant (=).
7) The maximum length of wires between the inverter and motor is 30 meters. If the wires are longer than 30
meters, set standard auto-tuning with the wires connected to improve low-speed torque during sensorless
vector control.
However the effects of voltage drop cause motor-generated torque in the vicinity of rated frequency to be
somewhat lower.
8) When a reactor is connected between the inverter and a motor, the motor's generated torque may fall.
Setting auto-tuning may also cause a trip () rendering sensorless vector control unusable.
5.12 Manual torque boost - increasing torque boost at low
speeds
 : Torque boost 1
• Function
If torque is inadequate at low speeds, increase torque by raising the torque boost rate with this
parameter.
Base frequency voltage
[Parameters]
Title
Torque boost 1

Valid when  is set to 0 (V/F constant) or 1 (square reduction)
Note 1: The optimum value is programmed for each inverter capacity. Be careful not to increase the torque boost
rate too much because it could cause an overcurrent trip at startup.


Function
0.0 - 30.0 (%)
E-21
Output frequency (Hz)
Base frequency 
Adjustment range
E6581595
5
Default setting
According to model
(See 11.4)