5 Conduit Entry Connectors, Plugs and Adapters

5.1 Procedures

It is the user/installer's responsibility to install the transmitters in accordance with national and local
code requirements. Conduit entry plugs and adapters shall be suitable for the environment, shall be
certified for the hazardous location when required and acceptable to the authority having jurisdiction
for the plant.
CONDUIT ENTRY PRECAUTIONARY NOTICE
THE CONDUIT/CABLE GLAND ENTRIES OF THIS PRODUCT ARE SUPPLIED WITH PLASTIC
DUST CAPS WHICH ARE NOT TO BE USED IN SERVICE.
IT IS THE USER'S RESPONSIBILITY TO REPLACE THE DUST CAPS WITH CABLE GLANDS,
ADAPTORS AND/OR BLANKING PLUGS WHICH ARE SUITABLE FOR THE ENVIRONMENT INTO
WHICH THIS PRODUCT WILL BE INSTALLED. THIS INCLUDES ENSURING COMPLIANCE WITH
HAZARDOUS LOCATION REQUIREMENTS AND REQUIREMENTS OF OTHER GOVERNING
AUTHORITIES AS APPLICABLE.
Use the following procedures for installation:
Step
1
Remove the protective plastic cap from the threaded conduit entry.
2
To ensure the environmental ingress protection rating on tapered (NPT), a
non-hardening thread sealant may be used.
Thread the appropriate size conduit connector or plug (M20 or ½" NPT) into
3
the conduit entry opening. Do not install conduit entry connectors or plugs in
conduit entry openings if adapters or reducers will be used.
4
Tighten plugs per the following table.
Description
M20 Conduit
½" NPT Conduit
Step
1
Remove the protective plastic cap from the threaded conduit entry.
2
To ensure the environmental ingress rating on tapered threads (NPT), a
non-hardening thread sealant may be used.
3
Thread the appropriate size adapter (M20 or ½ NPT) into the conduit entry
opening
4
Tighten adapters as per the following table.
Revision 10

Table 8 - Conduit entry connectors and plugs

10mm Hex Wrench
Entry
10mm Hex Wrench
Entry

Table 9 - Conduit Adapters

Description
½ to ¾ NPT
1 ¼" Wrench
Adapter
SMV800 Transmitter User's Manual
Action
Tool
32 Nm
32 Nm
Action
Tool
32Nm
Torque
24 lb-ft
24 lb-ft
Torque
24 lb-ft
Page 19