Installation in "Multi-Point" configuration (Daisy Chain)
Connect two wires from the RS.485
terminals of the control unit (LIN+
and
LIN-
terminals)
correspondent terminals of the first
device on the line.
Continue the wiring from the first
device to the subsequent one, and
so on.
Install the line end resistance (120-
150, 0.5W) on both the control
unit terminals and the terminals of
the last line device.
The maximum admitted length from
the control unit to the last device is
1.5km.
Use screened cable of appropriate
section 9574 or 9575 Belden type
LCD6000
LCD6000_manu-inst
+24V
to
the
EOL= 120
7
13
12
AM-2000
+24V
EOL= 120
11
17
16
AM-4000
+24V
EOL= 120
7
9
8
AM-6000
Typical RS.485 Multi-point connection (Daisy Chain) Shared Power
(
Installation manual
Doc. M-184.1-LCD6000T-ENG Rev A.2
Shared Power
–
GND
2 3
4 5
6 7
1
22
23
LCD-6000T
GND
2 3
4 5
6 7
1
30
31
LCD-6000T
GND
2 3
4 5
6 7
1
1
2
LCD-6000T
supply voltage of 24V central utilities
EOL= 120
3
1
2
4
5
6 7
LCD-6000T
EOL= 120
3
1
2
4
5
6 7
LCD-6000T
EOL= 120
3
1
2
4
5
6 7
LCD-6000T
)
PAGE - 15