Rs.485 Serial Line - Honeywell NOTIFIER LCD6000T Programming And Installation Manual

Repeater panel
Table of Contents

Advertisement

RS.485 serial Line

The LDC6000 panel is connected to the control unit through the RS.485 serial line.
The RS.485 line must be installed in "MULTI-POINT" configuration (daisy chain).
Each peripheral must be programmed with an address from 1  16. Refer to the installation manuals of each peripheral.
Installation in "Multi-Point" configuration (Daisy Chain)
 Connect two wires from the RS.485
terminals of the control unit (LIN+
and
LIN-
terminals)
correspondent terminals of the first
device on the line.
 Continue the wiring from the first
device to the subsequent one, and
so on.
 Install the line end resistance (120-
150, 0.5W) on both the control
unit terminals and the terminals of
the last line device.
 The maximum admitted length from
the control unit to the last device is
1.5km.
 Use screened cable of appropriate
section 9574 or 9575 Belden type
PAGE - 14
NOTIFIER ITALIA
EOL= 120
to
the
11
16
17
AM-4000
EOL= 120
11
16
17
AM-4000
EOL= 120
7
8
9
AM-6000
Typical RS.485 Multi-point connection (Daisy Chain) separate power
Note: Terminals 6 and 7 are not used on the LCD600T panel
Installation manual
Doc. M-184.1-LCD6000T-ENG Rev A.2
separate power
+24V GND
+24V
GND
1
2
3
4
30
31
LCD-6000T
+24V GND
1
2 3
4 5
6 7
LCD-6000T
+24V GND
1
2 3
4 5
6 7
LCD-6000T
+24V GND
EOL= 120
5
3
1
2
4
5
LCD-6000T
+24V GND
EOL= 120
3
1
2
4
5
6 7
LCD-6000T
+24V GND
EOL= 120
3
1
2
4
5
6 7
LCD-6000T
LCD6000
LCD6000_manu

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents