Zone Sounds & Timing - Honeywell ADEMCO VISTA-48D Installation And Setup Manual

Table of Contents

Advertisement

Installation Instructions
FIELD
TITLE and DATA ENTRIES
Powerline Carrier Device (X-10)
*27
House ID
0 = A
1 = B
2 = C
3 = D
4 = E
5 = F
Language Select
*28
0 = English
1 = Spanish
ECP Contact ID Output for ACM
*29
0 = not used
1 = use Contact ID output on ECP
Make Partition 3 a Common Area
*30
Partition
0 = no (must be 0 if system uses zone type
82 - Blockschloss)
1 = yes, make partition 3 a common area
partition
Zone Sounds & Timing
FIELD
TITLE and DATA ENTRIES
Single Alarm Sounding Per Zone
*31
Dialer/Bell Disable if Arm Stay
0 -7 = see table of entries at right
Fire Alarm Sounder Timeout
*32
0 = yes; fire sounder timeout after time
programmed in field ∗33
1 = no fire sounder timeout; continue
sounding until manually turned off
Bell (Siren) Timeout
*33
0 = No timeout
1 = 1 min
2 = 2 min
3 = 3 min
Exit Delay
*34
00 - 96 = 0 - 96 seconds
97 = 120 seconds
4-2
6 = G
# + 11 = L
7 = H
# + 12 = M
8 = I
# + 13 = N
9 = J
# + 14 = O
# + 10 = K
# + 15 = P
2 = Italian
3 = Portuguese
4 = 4 min
5 = 8 min
6 = 16 min
EXPLANATION
Powerline Carrier devices require a House ID, identified in this field.
Program Powerline Carrier devices in interactive modes ∗79, *80 and
*81.
Not intended for fire or UL installations.
Select the desired keypad display language.
UL installations must be 0 (English)
If selected, all messages programmed to go to the primary telephone
line receiver will also be sent (in Contact ID format) to the connected
Alternative Communication Media (ACM), such as a 7845i
Internet/Intranet Communicator or AI4164RS/AI4164ETH Eureka
Network Interface, or 7845C/7835C cellular radio (in selected
countries). The data line is supervised as well as certain functions in
a long range radio. If communication is lost or a trouble develops, an
attempt will be made to send a message via both ACM and telephone
to the central station.
Program the ACM for device address 3.
If selected, partition 3 functions as a common area partition, rather
than as an independent partition.
EXPLANATION
Select whether a zone going into alarm should sound more than once
/
per armed period and whether Bell and/or Dialer should be disabled if
armed STAY.
UL installations must be 0 (no limit).
Entry
Single Alarm
Sound
0
No UL: must be "0"
1
Yes
2
No
3
Yes
4
No
5
Yes
6
No
7
Yes
Select whether fire alarm sounding expires after sounder timeout or
remains until manually turned off.
UL fire alarm installations: must be 1.
This field determines whether the external sounder will shut off after
time allotted, or continue until manually turned off.
UL installations: For residential fire alarm installation, must be set
for a minimum of 4 min (option 4); for UL Commercial Burglary
installations, must be minimum 16 min (option 6).
The system waits the time entered before arming entry/exit zones. If
the entry/exit door is left open after this time expires, an alarm will
occur or the zone will be auto-bypassed, depending on the selection in
field *88. Common area zones use same delay as partition 1.
UL installations: For UL Commercial Burglar Alarm (Grade AA) and
UL Residential Burglar Alarm installations with line security, total
exit time must not exceed 60 seconds. For UL Burglar Alarm
installations without line security (Grade A), total exit time must not
exceed 120 seconds.
Disable Bell if
Disable Dialer if
Armed STAY
Armed STAY
No
No
No
No
Yes
No
Yes
No
No
Yes
No
Yes
Yes
Yes
Yes
Yes