Honeywell ADEMCO VISTA-48D Installation And Setup Manual page 44

Table of Contents

Advertisement

Installation Instructions
PROMPT
10 Zone Type
Perimeter
03
10 Partition
1
10 Report Code
1st 01 2nd 00 10
02 HARDWIRE TYPE
EOL
0
02 Response Time
1
10 INPUT TYPE
RF TRANS
3
5-2
VALID ENTRIES
Zone Type (ZT)
00-24, 77, 82, 90-93 = zone
type (see table at right)
Partition No. (P)
1-3 = partition
[∗] to continue
Report Code (RC)
First Digit: 1-9, 10 for 0, 11 for
B, 12 for C, 13 for D,
14 for E, 15 for F
00 to disable
Second Digit: same as above
[∗] to continue
Basic Wired Type
0 = EOL; 1 = NC; 2 = NO
3 = zone doubling (ZB)
4 = double-balanced (DB)
[∗] to continue
Response Time (RT)
0 = 10mSec
2 = 700mSec
1 = 400mSec 3 = 1.2 seconds
[∗] to continue
Input Device type (In)
2 = AW (Aux wired zone)
3 = RF (supervised RF
transmitter,
4 = UR (unsupervised RF
transmitter)
5 = BR (unsupervised button
type RF transmitter)
7 = RM (supervised RF motion
detector)
[∗] to continue
EXPLANATION
Each zone must be assigned to a zone type, which defines the way in
which the system responds to faults in that zone.
Enter the Zone Type code from the list below:
Note: If 00 is entered, Delete Zone ? will be displayed.
00 = Not used
07 = 24-Hr Audible
01 = Entry/exit #1
08 = 24-Hr Aux
02 = Entry/exit #2
09 = Fire
03 = Perimeter
10 = Interior w/Delay
04 = Interior Follower
12 = Monitor Zone
05 = Trouble Day/Alarm Night
14 = Gas
06 = 24-Hr Silent
16 = Fire w/Verify
*5800 button-type transmitters only
Enter the Partition number for this zone. Partition 1 is shown
entered.
Enter the report code for this zone, which consists of 2 hexadecimal digits,
each in turn consisting of 2 numerical digits. For example, for a report code
of "10," enter 01 and 00.
®
For Contact ID
, entering any non-zero entry as the first digit enables the
report code for this zone. Refer to the System Communication section for
information about report codes and formats.
This prompt appears only for zone numbers 02-08.
Zone 1 is automatically set for EOL operation.
This prompt appears only for basic wired zones 01-08 (zone 02 is used
as an example in display).
NOTE: If zone doubling is being used, the response time set for zones
01-08 automatically applies to each zone's associated doubled zone.
This prompt is skipped for zones 9-16 if zone-doubling was enabled at
"Hardwire Type" prompt.
All of the RF transmitters have one or more unique factory-assigned
input (loop) ID codes. Each of the inputs requires its own
programming zone (e.g., a 5804's four inputs require four
programming zones).
RF Transmitters can be enrolled as one of the following types:
Type
Description
"RF"
Sends periodic check-in signals, as well as
(Supervised RF)
fault, restore, and low-battery signals. The
transmitter must stay within receiver's range.
"UR"
Sends all the signals that the "RF" type
(Unsupervised RF)
does, but the control does not supervise the
check-in signals. The transmitter may therefore
be carried off-premises.
"BR" (Unsupervised Sends only fault signals. It does not send a
Button RF)
low-battery signal until it is activated. The
transmitter may be carried off-premises.
"RM"
Sends periodic check-in signals, as well as fault
(Supervised RF
and low- battery signals. The panel ignores
Motion Detector)
detector restore signals but automatically
restores the zone to "ready" after a few seconds.
Designed for facilities with multiple motion
detectors that may fault and restore
simultaneously. The transmitter
NOTES:
must remain within the receiver's range.
• For the built-in basic wired zones, the Input Device type is
automatically displayed as HW and cannot be edited.
• To change the input type of a previously programmed wireless
device (type RF, UR, BR, RM) to a wired zone (type AW), you must
first delete the transmitter's serial number
20 = Arm–STAY*
21 = Arm–AWAY*
22 = Disarm*
23 = No Alarm Resp
24 = Silent Burglary
77 = Keyswitch
81 = AAV Monitor Zone
82 = Blockschloss
90-93 = Configurable

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents