Reconfiguring The Fuel System; High Altitude Operation - Honeywell 10 kW Owner's Manual

Air-cooled, automatic standby geneators
Hide thumbs Also See for 10 kW:
Table of Contents

Advertisement

Available languages

Available languages

1.10

RECONFIGURING THE FUEL SYSTEM

To reconfigure the fuel system from NG to LP , follow these steps:
The primary regulator for the propane supply is NOT INCLUDED
with the generator. A fuel pressure of 10 to 12 inches of water
column (0.36 to 0.43 psi) MUST BE SUPPLIED to the fuel inlet
of the generator.
1.
Open the roof.
2.
For 10kW units: Loosen clamp and slide back the air inlet
hose.
• Slide fuel selector on carburetor out towards the back of the
enclosure (Figures 1.3 and 1.4).
• Return the inlet hose and tighten clamp securely.
For 12, 15 and 20kW units: remove the air cleaner cover.
• Slide the selector lever out towards the back of the enclosure
(Figures 1.5 and 1.6).
• Return the air cleaner cover and tighten the two thumb
screws.
3.
Close the roof.
4.
Reverse the procedure to convert back to natural gas.
Figure 1.3 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "In"
Position for
Natural Gas
Fuel
Figure 1.4 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "Out"
Position for
Liquid Propane
(Vapor) Fuel
NOTE:
Figure 1.5 - 12, 15 & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Fuel Selection Lever - "In" Position for Natural Gas Fuel
Figure 1.6 - 12, 15 & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Fuel Selection Lever - "Out" Position for Liquid Propane
(Vapor) Fuel
1.11

HIGH ALTITUDE OPERATION

The fuel system on this generator may be influenced by operation
at higher altitudes. Proper operation can be ensured by installing
an altitude kit when required. See the table below to determine
when an altitude kit is required. Operating this generator without
the proper altitude kit installed may increase the engine's emis-
sions and decrease fuel economy and performance. Kits may be
obtained from any Dealer, and should be installed by a qualified
individual.
General Information
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

12 kw15 kw20 kw

Table of Contents