JumpStart® Operation
6.2.9 Zone Trouble
Each zone has a Trouble LED (see Figure 6.1). The zone's Trouble LED will blink when specific SLC issues occur such as a missing device
or double address. Pressing the Silence Key will cause the zone trouble LED to be on solid. Once the zone trouble is corrected, the LED will
turn off.
6.3 JumpStart
Operation
®
The JumpStart feature will attempt to locate all SLC Mini-Monitor devices installed in the system, indicate all devices found on the FFT and
all FFT-24 Active LED's and allow the user to accept the configuration, repeat the JumpStart or allow the configuration to be discarded.
1.
To perform the FFT JumpStart press and hold the JumpStart button for 2 seconds.
2.
The FFT will search for installed SLC devices and activate the Active LED's of all zone/point addresses found.
3.
When the JumpStart is complete, the first four status LED's will blink. The user can now press the ACCEPT key causing the FFT to
save the configuration and restart.
4.
The user presses the JumpStart key again to repeat the SLC search process.
5.
If the user does not press the Accept key within one minute after the JumpStart is complete, its configuration will be discarded and the
FFT will be restarted.