SLC Device Installation
NOTE 1: Class A does not require the use of isolator modules.
.
NOTE 2: There are no T-taps allowed on Class A SLC loops.
CAUTION:
!
For proper system supervision do not use looped wire under terminals marked SLC + and – of the SLC device connectors. Break wire runs to
provide supervision of connections.

4.4 Addressing SK-MINIMON SLC Devices

All SK-MINIMON devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary dial to set the ones
place in a one or two digit number, and use the TENS rotary dial to set the tens place in a two digit number.
SK-MINIMON modules can be assigned any unique address from 1 to 48.
Example 1: To select device address 10, turn the ONES rotary dial to 0 and the TENS rotary dial to 1 as shown in Figure 4.4.
Example 2: To select device address 42, turn the ONES rotary dial to 2 and the TENS rotary dial to 4 as show in Figure 4.4.
22
Example 1: Device set to 10
Example 2: Device Set to 42
Figure 4.4 SK-MINIMON SLC Device Addressing using the Rotary Dials
Addressing SK-MINIMON SLC Devices
Model SK-FFT Manual — P/N 54711:B2 12/18/2020