Installing The Sk-Fft; Operating Power; Dip Switch Settings On Sk-Fft; 1: Dip Switch - Honeywell SK-FFT Installation & Operation Manual

Fire fighter's telephone
Table of Contents

Advertisement

Installation
5.
Connect one end of the wiring harness (P/N 130398 supplied) to the
Figure 3.8.
6.
Restore power. See Section 3.5.

3.4 Installing the SK-FFT

SK-FFT installation involves the following steps:
Make physical connection to any outputs that will power* the SK-FFT. (See Section 3.5).
Set the DIP switch ID for the SK-FFT (See Section 3.6.1).
*See Appendix A: in the back of this manual for compatible powering devices. Manuals can also be found on the website
www.silentknight.com.

3.5 Operating Power

This section provides instructions to install the appropriate DC power source.
1.
Connect the SK-FFT to the appropriate DC power source. See Section 2.4.1 for power requirements. For compatible
product see Appendix A.
2.
Use the on-board DIP switch to assign the configuration setting to the SK-FFT. (See Section 3.6.1).

3.6 DIP switch settings on SK-FFT

This section describes how to configure the DIP switch setting on the SK-FFT.
1.
Refer to Section 2.3 for location of the DIP switches on the SK-FFT board.
2.
Configure the SK-FFT module by adding it to the system through JumpStart feature. See Section 6.3 for JumpStart
Operation. Table 3.1 list possible DIP switch configurations.
3.6.1 DIP Switch
16
Figure 3.8 Wire Harness Connection from SK-FFT to FFT-24 Zones 25- 48
DIP Switch
1
SLC Devices Installed
2
Trouble PZT Enabled
3
SLC Class A Supervision
4
Phone Circuit Class A Supervision Phone Circuit Class B Supervision
5
First FFT-24 Expander Installed
Table 3.1 SK-FFT DIP Switch Configurations
SK
Figure 3.9 DIP Switch
ON
SLC Devices not Installed
Trouble PZT Disabled
SLC Class B Supervision
First FFT-24 Expander not Installed
Model SK-FFT Manual — P/N 54711:B2 12/18/2020
-FFT and the other end to the FFT-24 as shown in
SK-FFT
OFF
Installing the SK-FFT

Advertisement

Table of Contents
loading

Table of Contents