CAUTION: TO PREVENT THE RISK OF ELECTRICAL SHOCK AND DAMAGE TO THE UNIT, SHUT OFF THE POWER AT
!
THE CONTROL PANEL WHEN YOU INSTALL OR SERVICE THE CONTROL PANEL.

4.1 List of SLC Devices

The following SLC device can be used with the Fire Fighters Phone. See the device installation instructions for more information (packaged
with the device).
Device Part Number
SK-MINIMON
SK-ISO

4.2 Maximum Number of Devices

The SK-FFT supports up to 48 SK-MINIMON devices on one FFT system.

4.3 Wiring Requirements for SLC Device

The following information applies to the SK-MINIMON - Mini Monitor module.
4.3.1 Wiring SLC in (Class B) Configuration
No special wire is required for addressable loops. The wire can be untwisted, unshielded, solid or stranded as long as it meets the National
Electric Code 760-51 requirements for power limited fire protective signaling cables. Wire distances are computed using copper wire.
Maximum wiring resistance is 40 ohms to the farthest SLC device.
Maximum loop length depends on the wire gauge.
Figure 4.1 and Figure 4.2 show how length is determined for out and back tap T-Tap style wiring.
.
20

Section 4: SLC Device Installation

Mini Monitor Module
Fault Isolator Module
Wire Gauge
22 AWG
18 AWG
16 AWG
14 AWG
12 AWG
Figure 4.1 Calculating the Wire Run Length for a Simple Out and Back
Model Name/Description
Table 4.1
Max. Distance
1200 feet
3100 feet
4900 feet
7900 feet
10,000 feet
Model SK-FFT Manual — P/N 54711:B2 12/18/2020
T
Install Sheet PN
I56-3444-000
I56-3445-000