Honeywell SK-FFT Installation & Operation Manual

Honeywell SK-FFT Installation & Operation Manual

Fire fighter's telephone
Table of Contents

Advertisement

Quick Links

Model SK-FFT
Fire Fighter's Telephone
Installation/Operation Manual
Document 54711 Rev: B2
12/18/2020 ECN: 2907

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell SK-FFT

  • Page 1 Model SK-FFT Fire Fighter’s Telephone Installation/Operation Manual Document 54711 Rev: B2 12/18/2020 ECN: 2907...
  • Page 2 Heat detectors are designed to Limit-F-2020 protect property, not life. Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 3 Flexput®, Honeywell®, JumpStart®, Silent Knight®, and SWIFT® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered trademark of The Mozilla Foundation.
  • Page 4 Electrical and electronic equipment contains materials, parts and substances, which can be dangerous to the environment and harmful to human health if the waste of electrical and electronic equipment (WEEE) is not disposed of correctly. Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 5: Table Of Contents

    1.4: About This Manual ......................................7 Section 2: Prerequisites for Installation.......................... 8 2.1: Environmental Specifications ....................................8 2.2: Preventing Water Damage ....................................8 2.2.1: Removing the SK-FFT Assembly from the Housing ..........................8 2.3: SK-FFT Board Layout .......................................8 2.4: Electrical Specifications ....................................10 2.4.1: Power Requirements.....................................10 2.4.2: Current Ratings.....................................10...
  • Page 6 6.2.7: Status LEDs (on Inside of FFT dead front panel)..........................28 6.2.8: Zone Active ......................................28 6.2.9: Zone Trouble ......................................29 6.3: JumpStart® Operation .....................................29 Appendix A: Compatible Powering Devices ......................... 30 A.1: Compatible Power Devices.....................................30 Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 7: Section 1: Overview

    Authority Having Jurisdiction (AHJ). 1.4 About This Manual This manual is intended to be a complete reference for all installation and operations tasks for the SK-FFT. Honeywell Farenhyt series Instal- lation Manuals can be found on our web site at www.silentknight.com.
  • Page 8: Section 2: Prerequisites For Installation

    Do not mount in areas with humidity-generating equipment (such as dryers, production machinery) When selecting a location to mount the SK-FFT, the unit should be mounted where it will NOT be exposed to temperatures outside the range of 0°C- 49°C (32°F-120°F) or humidity outside the range of 10% - 93% at 30°C (86°F) non-condensing.
  • Page 9 Figure 2.2 SK-FFT Front View Active (green) Trouble (amber) Zone 33 - Zone 25 - Zone 41- Zone 40 Zone 32 Zone 48 Figure 2.3 FFT-24 Expander Front View for Zone 25 - 48 Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 10: Electrical Specifications

    Prerequisites for Installation Electrical Specifications 2.4 Electrical Specifications 2.4.1 Power Requirements Voltage for the SK-FFT must be a power-limited, filtered, non resettable nominal 24 VDC source. The voltage source must be within the range of 17-29 VDC. Circuits Voltage Current...
  • Page 11 Prerequisites for Installation Wire Routing Non-Power-limited Relay Circuit Power-Limited Non power-limited wiring must be run separately from power- limited wiring. Figure 2.4 Wire Routing Example Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 12: Section 3: Installation

    Section 3: Installation 3.1 Mounting the Cabinet Read the environmental specifications in Section 2.1 before mounting the SK-FFT cabinet. This will ensure that you select a suitable location. The cabinet can be surface or flush mounted. Do NOT flush-mount in a wall designed as a fire break.
  • Page 13 Figure 3.3 Trim Ring Around cabinet Secure the trim ring to the cabinet using the self-tapping sheet metal screws from the inside of the cabinet into the trim ring. Re-attach the cabinet door assembly. Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 14: Installing The Fire Fighter's Hand Set

    3.2 Installing the Fire Fighter’s Hand Set FFT Local Handset installation involves the following steps:  Insert phone cord through hole of dead front panel. See Figure 3.5. Figure 3.5 Handset Cord Inserted Through Dead Front Panel Hole Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 15: Fft-24 Installation

    Mount the FFT-24 on the six mounting studs located on the inside of the dead front panel and secure using the nuts removed from the blank plate. See Figure 3.7. mounting studs mounting studs Figure 3.7 Mounting Locations for the FFT-24 Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 16: Installing The Sk-Fft

    Refer to Section 2.3 for location of the DIP switches on the SK-FFT board. Configure the SK-FFT module by adding it to the system through JumpStart feature. See Section 6.3 for JumpStart Operation. Table 3.1 list possible DIP switch configurations.
  • Page 17: Fft Fire Fighter Telephone Module Connection

    3.7 SK-FFT Fire Fighter Telephone Module Connection The SK-FFT provides connection for a single Class B or Class A telephone audio circuit. See Section 4 and Section 5 for examples of audio zone configurations. A monitor module can be used to monitor the connection of the Fire Fighter Telephone remote handset (FFT-RHS) into the FFT-FPJ, which is then displayed on the SK-FFT active zone LED during the JumpStart feature.
  • Page 18: Fft-Fpj Installation

    Attach system wiring to the terminal strip on the telephone chassis assembly Install 6-32 nut in backbox. Do not tighten. Install telephone chassis assembly in backbox. Install trim ring on backbox with 6-32 wing nuts. Do not tighten. Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 19 Installation Installation of FFT-STS Install door assembly. Tighten wing nuts. Contact EOL set to Connected *See Figure 3.14 for EOL Figure 3.13 FFT-STS Telephone Connection Figure 3.14 EOL Example Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 20: Section 4: Slc Device Installation

    I56-3445-000 Table 4.1 4.2 Maximum Number of Devices The SK-FFT supports up to 48 SK-MINIMON devices on one FFT system. 4.3 Wiring Requirements for SLC Device The following information applies to the SK-MINIMON - Mini Monitor module. 4.3.1 Wiring SLC in (Class B) Configuration No special wire is required for addressable loops.
  • Page 21: 2: Wiring Slc Devices In (Class A) Configuration

    Figure 4.2 Calculating Wire Run Length for a T-tap 4.3.2 Wiring SLC Devices in (Class A) Configuration Figure 4.3 illustrates how to wire the SLC loop for Class A installations. . Figure 4.3 Class A SLC Configuration Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 22: Addressing Sk-Minimon Slc Devices

    Example 2: To select device address 42, turn the ONES rotary dial to 2 and the TENS rotary dial to 4 as show in Figure 4.4. Example 1: Device set to 10 Example 2: Device Set to 42 Figure 4.4 SK-MINIMON SLC Device Addressing using the Rotary Dials Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 23: Section 5: Audio Phone Circuit Installation

    Table 5.1 Devices 5.2 Maximum Number of Devices The SK-FFT supports up to 48 zones. Each zone consists of one addressable monitor module (SK-MINIMON) and a minimum of one Fire Fighter Telephone Jack (FFT-FPJ). 5.3 Wiring Requirements for the Audio Telephone Circuit The following information applies to the FFT-FPJ Fire Fighter Phone Jack.
  • Page 24: 2: Single Phone Jack Audio Circuit Wired In Class A Configuration

    For information on the wiring specifications, see section 5.3.1. Figure 5.3 illustrates the phone jack audio circuit (Class A) and SLC for (Class A) configuration. Contact EOL Connected Figure 5.3 Single Phone Jack Audio Circuit in Class A PRELIMINARY: Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 25: 3: Multi-Phone Jack Audio Circuit Wired In Class B Configuration

    Break wire run to provide supervision of communications. 4.7K W, 1/2 watt ELR (Install on the last device for Class B telephone circuit only). Figure 5.4 Multi-Phone Jack Audio Circuit Wired in Class B PRELIMINARY: Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 26: 4: Multi-Phone Jack Audio Circuit In Class A Configuration

    To configure the FFT for Telephone Jack only, the DIP Switch position 1 must be off (SLC Devices not Installed). See Table 3.1. Audio wiring for this configuration is detailed below. See Figure 5.6 and Figure 5.7. PRELIMINARY: Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 27 (Install on the last device for Class B telephone circuit only). Figure 5.6 Telephone Jack Only Audio Circuit Wired in Class B Figure 5.7 Telephone Jack Only Audio Circuit Wired in Class A PRELIMINARY: Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 28: Section 6: System Operation

    Section 6: System Operation The operation of the SK-FFT Fire Fighter Telephone System allows the audio communication from 24 remote connections through remote handsets from a single local handset. Up to 10 remote handsets can be connected and communicating at one time. The remote audio connec- tions can be expanded to 48 with the optional FFT-24 Zone Expander.
  • Page 29: 9: Zone Trouble

    The user presses the JumpStart key again to repeat the SLC search process. If the user does not press the Accept key within one minute after the JumpStart is complete, its configuration will be discarded and the FFT will be restarted. Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 30: Appendix A: Compatible Powering Devices

    Appendix A: Compatible Powering Devices A.1 Compatible Power Devices Table A.1 lists the available Honeywell Silent Knight series compatible power devices used with the SK-FFT. Model Manual PN 5820XL / 5820XL-EVS Addressable Fire Control Panel / Emergency Voice 151209 /...
  • Page 31 Return Material Authorization form. The replacement part shall come from Manufacturer's stock and may be new or refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM. Warn-HL-08-2009.fm PRELIMINARY: Model SK-FFT Manual — P/N 54711:B2 12/18/2020...
  • Page 32 Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 54711 | B2 | 06-21 www.silentknight.com ©2021 Honeywell International Inc.