3.1 Mounting the Cabinet

Read the environmental specifications in Section 2.1 before mounting the SK-FFT cabinet. This will ensure that you select a
suitable location.
The cabinet can be surface or flush mounted. Do NOT flush-mount in a wall designed as a fire break.
3.1.1 Surface Mounting
The Cabinet can be mounted on the wall surface by using the mounting holes in the back of the cabinet (see Figure 3.1 on
page 12).
1.
Insert two screws level with each other, 14" apart for the top cabinet key shaped holes. See Figure 3.1 on page 12.
2.
Hang the cabinet onto the two screws. Tighten the screws down.
3.
Insert two screws into the two bottom mounting holes and tighten them snug to the cabinet.
3.1.2 Flush Mounting
This section describes how to flush mount the cabinet into a wall. To recess mount the cabinet you will need to have the
optional trim ring P/N VIP-TR (ordered separately).
Follow these steps to recess mount the cabinet:
1.
Remove the cabinet door and the dead front panel.
2.
Cut a recess hole 20-1/4" W x 26-3/4" H (51.44 cm W x 67.95 cm H). There should be 1.5" to 1.75" of cabinet extruding
from the wall, this should be measured from either the top edge or bottom edge to the exterior side of the sheet rock. (See
Figure 3.2.)
NOTE:
Do not insert the cabinet deeper than recommend above. If the cabinet is mounted to deep you will not be able to re-attach the door
assembly.
3.
Mount the cabinet to wall studs by inserting a screw through the cabinets side mounting holes into the wall stud.