Devices

17.1 Processor board

The processor board is connected directly to the zone board by a 64 plug connector. On the processor board
we find, among other things, the microprocessor for controlling the panel functions as well as the operating
system and the customer data EEPROM.
The communication transponder is attached to the plug-in contacts X3, X4 of the processor board. The
connection to the analog loop of the fire alarm system 8000 / IQ8Control, the esserbus
terminal strip X27. The display and control panel is connected to the processor board via a ribbon cable
connection at terminal X12.
terminal
connection for
esserbus
®
external PC
-ULout -U Lin +UL +UL
X27
X3
X4
position for esserbus
®
-
communication transponder
Fig. 23: Processor board / position of the subassemblies
X3, X4
Slot for the esserbus
Plug for the ribbon cable to the display and control panel
X12
X13
64-pole terminal strip for connecting to the zone board
X27
Terminals for the esserbus
X28
4-pole programming interface for Service PC
Terminals for the e contact of the housing door
X29
U17
Operating system and customer data EEPROM
S1
Reset button (cold start) - press this button to reset the panel.
S2
Service key

17.1.1 Stop extinguishing procedure for test purposes by the operator

To interrupt a running extinguishing procedure for test purposes hold down the S2 button (service)
and briefly push the S1 (RESET) button as well.
86
SERVICE
S2
X28
U17
®
communication transponder (Part No. 808615)
®
analog loop
®
, is made via the 4-pole
to control and display panel
X12
S1
RESET
processor board
X13
X29
FB 798352 / 11.07