17.2 Zone board

The zone board allows eight alarm zones to be connected for automatic fire detectors series 9000 and/or 9100
as well as manual call points (MCP).
The alarm zone operating mode (standard or EDD) is set via the associated plug-in jumpers (J1 to J8). Mixed
operation on one alarm zone of series 9000 and 9100 automatic fire detectors is not permissible.
X2
N
PE
L1
TRAFO PRIMÄR
F2
X5
X1
T1A
F1
T4A
X3
+ - + - + - + - + -
MAN.
EM.
X4
ALARM
STOP
Fig. 24: Zone board / position of the subassemblies
Five technical zones are available for non-automatic detectors (manual call points, push-button controls) and
inputs for connecting trouble contacts.
When connecting the mains voltage and the protective earth, refer to the instructions in the
chapter "Mains connection and earthing".
FB 798352 / 11.07
connection prozessor card
Std.
Std.
EDD
EDD
+ -
+ -
FAILURE
detector zone 7
detector zone 8
EXTRA
EXTING.
BLOCKING
RELEASE
System 1
Extinguishing Control Computer 8010 - Series 2
X16
Zone card
Std.
Std.
Std.
Std.
EDD
EDD
EDD
EDD
+ -
+ -
+ -
detector zone 6
detector zone 5
detector zone 4
Std.
Std.
EDD
EDD
+ -
+ -
+ -
DZ 14
+ -
detector zone 3
detector zone 2
detector zone 1
BUZZER
OFF
J9
groung fault
identification
DZ 15
+ -
RESET
87