3. Specifications
Item
Operating temperature
Storage temperature
Relative humidity
Vibration resistance
Shock resistance
Grounding
Ambient air
Corrosive gas
Altitude
Radioactivity
Cooling
Mount base (HSC-1770)
Power supply module (LQV410)
CPU module (LQP600)
RI/O-IF module (LQE950)
OD.RING module (LQE510-E)
J.NET module (LQE540-E)
FL.NET module (LQE702-E)
D.NET module (LQE770-E)
ET.NET module (LQE260-E)
Mount base mounting screws
Module mounting screws
Mount base FG terminal screws
Terminal block mounting screws
Connecting screws
Mounting screws for power supply
module terminal block cover
#: When installing the system in a location that is subject to constant vibration, implement anti-vibration measures for
the control panel.
Table 3-1 General specifications
Specification
0 to 55°C
-20 to 75°C
10 to 90% RH (whether operational or
non-operational)
Frequency of 10 to 150 Hz, acceleration
2
of 10 m/s
Sweep time of 8 minutes per cycle in the
X, Y, and Z directions
Number of sweep cycles: 20
Peak acceleration of 147 m/s
Half sinusoidal impact wave time of 11
ms, three times each in X, Y, and Z
directions
Class D grounding with the ground
resistance of 100Ω or less
3
Dust: 0.1mg/m
JEITA IT-1004A Class B
1,000 m or below
--
Natural-air cooling
1,300 g or less
1000 g or less
450 g or less
320 g or less
410 g or less
370 g or less
275 g or less
330 g or less
380 g or less
1.5 N
•
m
1.0 N
•
m
0.6 N
•
m
3-1
2
or less
3. Specifications
Remarks
Temperature variation of no
more than 10°C per hour
Condensation must be
strictly avoided.
JIS C 60068-2-6 compliant
The system must not be
installed in a location that is
subject to constant
#
vibration
.
JIS C 60068-2-27 compliant
The environment must be
free of corrosive gas.
The environment must be
free of radioactivity.
M5 screws
M4 screws
M3 screws