Programming Software; General Specifications; Power Supply Specifications - Hitachi HX-CP1S08-0 Instruction Manual

Stand-alone cpu unit
Table of Contents

Advertisement

 Programming software
HX requires programming software.
HX-CODESYS is required for all models. HX-Studio is required for hybrid model.
Product name
Part number
HX-CODESYS
HX-CDS
HX-Studio
HX-STD
*1
*1 Only the hybrid model is required.
Windows  are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or other countries.
CODESYS is registered trademarks of 3S-Smart Software Solutions GmbH.
EtherCAT  is registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.
Ethernet is registered trademarks of Fuji Xerox Co., Ltd.
 General Specifications
Item
Operational temperature
Storage temperature
Operational humidity
Storage humidity
Vibration resistance
Shock resistance
Usage environment
Structure
Cooling
 Power supply Specifications
Item
Rated input voltage
Input voltage range
Input current
Instantaneous power failure guarantee
Input rush current (At 24 V DC)
Noise resistance
Grounding
Output overcurrent protection
Isolation
Efficiency
!
CAUTION
Because the varistor is connected to power supply circuit of HX, do not test insulation resistance and withstand voltage.
If insulation resistance and withstand voltage of equipment that installed HX is tested, remove all wiring connecting to HX.
IEC 61131-3 full compliant programming software with ST (Structured Text),
SFC (Sequential Function Chart), FBD (Function Block Diagram ),
LD (Ladder Logic Diagram) and IL (Instruction List).
Multilingual support (Japanese, English, German, Spanish, French, Italy, Russian, Chinese)
Supported operating system: Windows  7 SP1 or newer
Eclipse 4.6 Neon CDT 9.1.0 base IDE for Hybrid model application
Programming language: C / C++, Connection means to HX-CPU: Ethernet
Supported operating system: Windows  7, 8, 8.1, 10 (32 / 64 bit)
(IEC 61131-3 compliant HX-CODESYS (HX-CDS) is included in DVD)
AC-DC power supply
24 V DC
21.6 to 26.4 V DC
0.4 A or less
1 ms or less
Noise voltage 1,500 Vpp, Noise pulse width 100 ns, 1 μs (Noise input by a noise
-
simulator across input terminals of a power module according to measuring method
of Hitachi-IES.
-
Static noise 3,000 V at electrode part
Specification
Specification
0 to 55 °C
-10 to 75 °C
5 to 95 % RH (no condensation)
5 to 95 % RH (no condensation)
Conforms to IEC 60068-2-6
Conforms to IEC 60068-2-27
No corrosive gases, no excessive dust
Open wall-mount type
Natural air cooling
Specification
25 A or less (Ta=25 °C)
Ground with 100 Ω or less
Output short-circuit protection
Non isolated
85 % or more
- 5 -
AC adapter
12 V DC
10.8 to 13.2 V DC
0.7 A or less
No guarantee
NJI-672B(X)