The LCD2-80 & Terminal Mode
8-position DIP switch (SW3)
1)Set "ON" to lock the Control
Keys.
2)Set "ON" to disable Piezo.
3)Set "ON" for communication
with panels release 14 and
later) that support the LCD2-
80.
4)Set "ON" to connect to PC
for updating LCD2-80
firmware.
5)Set "ON" for last LCD2-80.
6)Not used.
7)EIA-485 Termination. Set
"ON" in this mode.
8)EIA-485 Termination. Set
"ON" in this mode.
AKS-1B Keyswitch Interface (J2)
Connect to optional keyswitch.
Figure 2.1 Configuring the
10
4
3
TB2
2
1
7
6
5
TB1
4
3
2
1
Terminal Mode Connections
LCD2-80
LCD2-80 Instruction Manual — P/N 53242:A 08/18/2009
SW1 & SW2
Address Switches
(Future Use)
-EIA-485 In
-EIA-485 Out
+EIA-485 In
+EIA-485 Out
No connection
Reference
System Common Out
System Common In
+24 Volts Out
+24 Volts In
No connection
for TERMINAL Mode