Honeywell Gamewell FCI ILI-MB-E3 Product Installation Document page 13

Intelligent loop interface-main board
Table of Contents

Advertisement

Designation
Description
W4
ARCNET Termination
W5
RS-485 AUX Interface
Termination
J7
RS-485 Transceiver Port
Head
NOTE 1: Must be IN when connected via ribbon cable from this ILI-MB-E3 at J1 to a PM-9/PM-9G connector J1. Requires the
removal of the JMP-1 on the PM-9/PM-9G. Must be OUT when a ribbon cable is not installed in J1 and the ground fault detection
is being provided by an INI-VG Series (First/Second/Third Generation) node that is being powered from a common PM-9/PM-9G.
NOTE 2: Connect J1 to PM-9/PM-9G J1 only when the PM-9/PM-9G is NOT powering an INI-VG Series (First/Second/Third
Generation) sub-assembly.
NOTE 3: Use ILI-MB-E3 Auxiliary RS485 Port (TB3-1 COM A & TB3-2 COM B) to connect to the LCD-E3 (E3 annunciator
module), LCD-SLP (E3/S3 annunciator module), LCD-7100/RAN-7100 (7100 Remote Annunciator Module), ASM-16
(Addressable Switch Module), ANU-48 (LED Annunciator Driver Module) or DACT-E3 (E3 Digital Communicator Transmitter).
NOTE 4: RPT-E3-UTP (E3 Repeater Module) is required when this ILI-MB-E3 is networked via ARCNET to any of the following:
- INI-VGE, INI-VGC, INI-VGX, (First/Second/Third Generations)
- Another RPT-E3-UTP equipped node
In addition, when the ILI-MB-E3 is connected to an NGA (whether the NGA is local or remote), the RPT-E3-UTP is required. It is
not required for LOCAL ARCNET communication within a single enclosure. (J2 or J5).
NOTE 5: For Style 4 use terminals B+ and B- only. For Style 6 use terminals B+ and B- and connect return wires to A+ and A-. For
Style 7, wire as for Style 6 and use Isolator Modules and or Isolator Detectors per recommendations as required.
NOTE 6: NAC1 and NAC2 are rated as 2.0 A Special Application and 0.2 A Regulated.
NOTE 7: When used for Releasing, must be configured in CAMWorks™ for Releasing in the General Settings Section.
NOTE 8: Use the ANX for Fire applications only.
NOTE 9: The PRN-7 Printer is a dot-matrix printer. It is shipped with a DB-9 Adapter Kit that provides the necessary hardware and
cables for installation. For additional information on the PRN-7 Printer, refer to the Manufacturer's Installation Guide.
ILI-MB-E3 Product Installation Document — P/N 9000-0579:M7 07/02/2018
ILI-MB-E3 (Second Generation) Wiring Designations
OFF = If the ILI-MB-E3 is located in the middle of the bus or if it is not
used.
ON = If the ILI-MB-E3 is located at either end of the ARCNET bus.
OFF = Normal Operations
ON = ON (RS-485 Termination) (Use if the last device on RS-485 bus
also has its termination jumper shorted. Bus termination is
recommended, as it improves noise rejection).
Use the 10-pin ribbon cable to connect from J7 of the ILI-MB-E3 to J5
of the LCD-SLP display.
Table 3.5.1.1 ILI-MB- E3 Wiring Designations (Continued)
Comments
Notes
Used for
ILI-MB-E3,
(Second
Generation)
only.
13