Honeywell Gamewell FCI ILI-MB-E3 Product Installation Document page 12

Intelligent loop interface-main board
Table of Contents

Advertisement

Designation
Description
TB4-7
SLC 1 B-
TB4-8
SLC 1 B+
TB5-1
Alarm DC NC
TB5-2
Alarm DC NO
TB5-3
Alarm DC Common
TB5-4
Supv DC NC
TB5-5
Supv DC NO
TB5-6
Supv DC Common
TB5-7
Trbl DC NC
TB5-8
Trbl DC NO
TB5-9
Trbl DC Common
TB6-1
RS-232 GND
TB6-2
RS-232 TxD
TB6-3
RS-232 Supervision
TB6-4
RS-232 RxD
W1
Factory Jumper
For W2 thru W5 and J7, refer to the subsections: ILI-MB-E3 (First Generation) and ILI-MB-E3 (Second Generation) sections.
W7, W8
Municipal Jumpers
W9
Ground Fault Detection
SW2-1
Switch
SW2-2
Switch
SW2-3
Switch
SW2-4
Switch
SW2-5
Switch
J1
ILI to PM-9/PM-9G
COMM Port
J2
Local ARCNET
J4
ARCNET Repeater
Connector
J5
Local ARCNET
W2
Factory Jumper
W3
Factory Jumper
W4
ARCNET Termination
W5
RS-485 AUX Terminal
12
ILI-MB-E3 (First and Second Generation) Wiring Designations
SLC 1 Style 4 / 6 / 7 Out (See Note 5)
SLC 1 Style 4 / 6 / 7 Out (See Note 5)
Alarm relay contact, N/C
Alarm relay contact, N/O
Alarm relay contact, Common
Supervisory relay contact, N/C
Supervisory relay contact, N/O
Supervisory relay contact, Common
Trouble relay contact, N/C
Trouble relay contact, N/O
Trouble relay contact, Common
For Programming, GND connects to red lead on the download cable P/
N 75267. For Printer Port, GND connects to printer DB-9, PIN-5.
For Programming, TxD connects to black lead on the download cable
P/N 75267. For Printer Port, TxD connects to printer DB-9, PIN-2.
Optional Printer Supervision.
For Printer Port, SUPV connects to printer DB-9, PIN-4.
For Programming, RxD connects to green lead on the download cable
P/N 75267. For Printer Port, RxD connects to printer DB-9, PIN-3.
Factory Use Only (Default OUT)
"MB"
= For Master Box / Releasing
"PR"
= For Polarity Reversal (See Note 7)
IN
= ENABLE
OUT
= DISABLE (See Note 1)
1 ON = SLC 1 DISABLED
(OFF = SLC 1 ENABLED)
2 ON = SLC 2 DISABLED
(OFF = SLC 2 ENABLED)
3 ON = NAC 1 & 2 DISABLED
(OFF = NAC 1 & 2 ENABLED)
4 ON
= BUZZER DISABLED
(OFF = BUZZER ENABLED)
5 ON = RS-232 115.2 K BAUD
(OFF = defined by CAMWorks™)
Connects to PM-9/PM-9G J1. (See Notes 1 & 2)
Connects to J5 of the next ILI-E3, ILI95-E3 Series or ANX sub-assembly.(See Note 8)
Connects to INI-VG Series (First/Second/Third Generation) J7 or J10 of the RPT-E3-UTP
(See Note 4).
Connects to J2 from the previous ILI-E3, ILI95-E3 Series or ANX sub-assembly.
(See Note 8).
ILI-MB-E3 (First Generation) Designations
Factory Use Only (Default OUT)
Factory Use Only (Default OUT)
OPEN = Normal Operation
SHORT = If the ILI-MB-E3 is located at the end of the ARCNET bus.
OPEN = OFF
SHORT = ON (RS-485 Termination)
Table 3.5.1.1 ILI-MB- E3 Wiring Designations (Continued)
ILI-MB-E3 Product Installation Document — P/N 9000-0579:M7 07/02/2018
Comments
RS-232
Download
or Printer Port
(See Note 9).
Used for the
ILI-MB-E3, (First
Generation) only.

Advertisement

Table of Contents
loading

Table of Contents