Honeywell Gamewell FCI ILI-MB-E3 Product Installation Document page 11

Intelligent loop interface-main board
Table of Contents

Advertisement

3.5 ILI-MB-E3 Wiring Connections
Figure 3.5.1 illustrates the ILI-MB-E3, (First Generation) and Figure 3.5.2 illustrates the ILI-MB-E3, (Second Generation).
ILI-MB-E3 (First Generation)
TB3
TB2
TB1
Figure 3.5.1 ILI-MB-E3 (First Generation) Module
3.5.1 ILI-MB-E3 Wiring Designations
Table 3.5.1.1 illustrates the ILI-MB-E3 terminal designations for the First and Second Generation versions.
Designation
Description
TB1-1, TB1-3 +24 V IN
TB1-2, TB1-4 GND
TB2-1
NAC 1 B+
TB2-2
NAC 1 B -
TB2-3
NAC 1 A+
TB2-4
NAC 1 A-
TB2-5
NAC 2 B+
TB2-6
NAC 2 B-
TB2-7
NAC 2 A+
TB2-8
NAC 2 A-
TB3-1
AUX RS-485 A
TB3-2
AUX RS-485 B
TB3-3
Earth Ground
TB3-4
Resettable B+
TB3-5
GND
TB3-6
Non-resettable B+
TB3-7
GND
TB3-8
Municipal Ckt+
TB3-9
Municipal Ckt -
TB4-1
SLC 2 A-
TB4-2
SLC 2 A+
TB4-3
SLC 2 B-
TB4-4
SLC 2 B+
TB4-5
SLC 1 A-
TB4-6
SLC 1 A+
ILI-MB-E3 Product Installation Document — P/N 9000-0579:M7 07/02/2018
ILI-MB-E3 (First and Second Generation) Wiring Designations
+24 VDC Input from PM-9/PM-9G TB4-1
Common negative from PM-9/PM-9G TB4-2
Notification Appliance Circuit 1 (See Note 6)
Notification Appliance Circuit 1 (See Note 6)
Notification Appliance Circuit 1 (See Note 6)
Notification Appliance Circuit 1 (See Note 6)
Notification Appliance Circuit 2 (See Note 6)
Notification Appliance Circuit 2 (See Note 6)
Notification Appliance Circuit 2 (See Note 6)
Notification Appliance Circuit 2 (See Note 6)
Output to LCD-E3, LCD-SLP, ASM-16, ANU-48, LCD-7100/RAN-7100, DACT-E3
(See Note 3)
Output to LCD-E3, LCD-SLP, ASM-16, ANU-48, LCD-7100/RAN-7100, DACT-E3
(See Note 3)
Connect to water pipe ground
Auxiliary resettable 24 VDC power
Common negative
Auxiliary non-resettable 24 VDC power Wire TC810S1000 releasing control module @
24VDC to non-resettable B+ (System Common).
Common negative
Output to Local Energy City Box, Remote Station or Releasing Solenoid - Non Power-
limited (See Note 7)
Output to Local Energy City Box or Remote Station or Releasing Solenoid - Non Power-
limited (See Note 7)
SLC 2 Style 6 / 7 Return (See Note 5)
SLC 2 Style 6 / 7 Return (See Note 5)
SLC 2 Style 4 / 6 / 7 Out (See Note 5)
SLC 2 Style 4 / 6 / 7 Out (See Note 5)
SLC 1 Style 6 / 7 Return (See Note 5)
SLC 1 Style 6 / 7 Return (See Note 5)
Table 3.5.1.1 ILI-MB- E3 Wiring Designations
ILI-MB-E3 (Second Generation)
TB3
TB4
TB2
TB5
TB1
TB6
Figure 3.5.2 ILI-MB-E3 (Second Generation) Module
Comments
J5
J2
J4
SW 2
SW 1
TB4
TB5
TB6
J1
11