This Manual must be carefully read by all individuals who have or will have the responsibility of using,
maintaining, or servicing this product. The product will perform as designed only if it is used,
maintained, and serviced in accordance with the manufacturer's instructions. The user should
understand how to set the correct parameters and interpret the obtained results.
Only use the Honeywell-specified rechargeable lithium-ion battery pack supplied with the
instrument.
Charge the instrument Li-ion battery using the specifically supplied charger and only outside
hazardous areas. The maximum voltage from the AC charger Um must not exceed 6.0 VDC.
The battery pack can only be changed in a non-hazardous area. Only use approved
rechargeable battery pack P/N 500-0165-000 produced by Honeywell.
Any data download device connected to this instrument must be approved SELV or Class 2
equipment.
Use of non-Honeywell components will void the warranty and can compromise the safe
performance of this product.
Warning: Substitution of components may impair safe performance of this product.
When changing the sensor configuration, ensure the operator is aware of any changes to
certification restrictions
SPECIAL CONDITIONS FOR SAFE USE
This multi-gas monitor must be calibrated if it does not pass a bump test, when a new sensor
has been installed, or at least once every 180 days, depending on use and sensor exposure to
poisons and contaminants
The AC charger system of BW RigRat shall only be applied in non-hazardous areas by
charger specifically supplied for use with the unit (for example model number ADS-25SGP-06
05717E, manufactured by HONOR Electric), approved as SELV or Class 2 equipment against
IEC 60950 or an equivalent IEC standard. The maximum voltage Um from the charger shall
not exceed DC 6.0V.
The BW RigRat enclosure has an ingress protection of rating of IP-54. The user shall ensure
that the external plugs that used for IS charger, 4-20mA input, and ON-OFF switch will provide
a degree of protection of IP-54, after they are connected to the sockets.
Do not open when an explosive atmosphere is present.
Note: Users are recommended to refer to ISA -RP12.13, Part II-1987 for general information on
installation, operation, and maintenance of combustible gas detection instruments.