Honeywell Centraline FALCON User Manual page 249

Table of Contents

Advertisement

USER GUIDE
RESULT:
After selecting the System Status event enrollment, the Event
Enrollment Details dialog box displays. The Alarming tab is
selected by default. Here the following algorithmic reporting
settings defined in CARE are displayed:
• Notification Class
• Notify Type
• Event State
• Transitions (Acknowledged status and time and date of last
transition)
• Event Type
• BACnet Property State
• BACnet Device State(s) (=Off-Normal-States)
You only can select the transitions to be reported and set the
delay time.
4. Under Transitions, check the transition events that should trigger the event
enrollment alarming. Refer to the relevant To-Off-Normal transitions listed under
BACnet Device State(s).