Abnormal Stop Procedures - Honeywell 200 Series Hardware Manual

Table of Contents

Advertisement

1.
SECTION II.
OPERATOR'S CONTROL PANEL
Repeat steps "e" through "h" as many times as there are
characters to be written into successive memory locations.
4.
To trace program flow manually:
a.
Set the CONTROL buttons to designate the sequence register
(octal 17), unless this register is already designated.
b.
Press the CONTROL DISPLAY button {to display the current
operation code.
c.
Press the INSTRUCT button (to execute the instruction).
d.
Repeat steps "e" and "c" the desired number of times.
5.
To perform a BOOTSTRAP and RUN operation:
a.
Press the INITIALIZE button.
b.
Press the ADDRESS buttons (to designate the starting loca-
tion in main memory,
if
different from zero).
c.
Press the CONTENTS buttons to designate the desired pe-
ripheral control.
d.
Prepare the periphe ral device de signated in "c" above (i. e. ,
cycle up the device) to accept a PDT instruction which will
read in the loading program.
e.
Press the BOOTSTRAP button and wait for the STOP indi-
cator to illuminate.
f.
If the program being loaded is written for other than two-
character addressing mode, press the appropriate ADDRESS
MODE button to select the proper addressing mode.
NOTE:
It
is usually not necessary to manipulate the AD-
DRESS MODE buttons, since the program usually
contains the appropriate instruction for address-
ing mode control.
g.
Press the RUN button.
Abnormal Stop Procedures
The control panel power indicators {viz., VOLTAGE, FAN, andCB), the PARITY indicator,
and the PROGRAM indicator signal abnormal stop conditions.
The operating procedures for
each of these occurrences is outlined below.
VOLTAGE
FAN
CB
PARITY
If a VOLTAGE indication occurs, the system ordinarily stops opera-
ting altogether.
In this case, the service engineer should be called.
The FAN indicator may flicker intermittently at times during nor-
mal operations, but if the indicator illuminates and remains con-
stant (in which case the system powers down), a service engineer
should be called.
Illumination of the CB indicator denotes a circuit breaker actuation,
in which case the system ceases operation.
In this event, the ser-
vice engineer should be called.
When a PARITY indication occurs, central processor operations
stop and cannot be resumed normally by simply pressing the RUN
2-15

Advertisement

Table of Contents
loading

This manual is also suitable for:

120121

Table of Contents