Commissioning information
S4 Beam Sensor & brackets
(for Vigilon and Nano Systems)
This document describes how to adjust the
beam sensor using adjusters on the angle or
parallel bracket, align beam sensor pairs and
test the installation.
Transmitter (red retainer) Receiver (black retainer)
A beam sensor pair consist of a:
¨
'beam transmitter' that can be identified by
a red lens retainer and a
¨
'beam receiver' that can be identified by a
black lens retainer.
¨
each sensor is fitted onto a base that is a
part of an angle or parallel bracket.

Compatibility

The S4 Beam Sensor pair are compatible for
use in Vigilon and Nano systems having the
following panel firmware.
Control
having card and firmware
Panel
Vigilon
Main Controller Card
³ V4.41 / V3.96
Loop Processor Card
³ V4.39 / V3.96
Nano
Main Controller
³ V1.39
Loop Driver
³ V1.03

Backward Compatibility

An S4 Beam sensor pair can be converted to
be a BACKWARD COMPATIBLE Beam
Sensor pair.
The conversion is done using a Programming
base interface for S4 beam sensor pair, see
section headed 'Backward Compatibility'.
4188-968 issue 4_Part 2_07-12_S4 mains interface

Commissioning checks

Compatibility
Check the control panel in the system has compatible software for
the S4 beam sensors installed on its loop circuit.
Brackets
If necessary, check the method of adjusting the parallel and angle
brackets.
Laser tool
Read the instructions supplied with the recommended laser tool
and roughly align the beam sensor using the tool.
Light shield
A light shield is only required to be fitted onto a beam receiver where
direct sunlight or strong light is likely to fall in the path of the 'beam
receiver'. Where necessary fit the light shield.
Normal indications
Check the operational indications given by the red LEDs on the
beam sensor.
Find Beam
Finding the device address of the 'beam transmitter' and
'beam receiver' on the loop.
Beam STATES
Determine which Beam sensor STATE is required.
Select a STATE
Program the required Beam sensor STATE, the factory default
is STATE 0.
Alignment indications
Interpreting the alignment indications given at a beam device.
Align beam sensor pair
Align the 'beam transmitter' with 'beam receiver'.
Time averages
Reading the time averages during beam sensor alignment.
Gain and STATE
Check the Beam STATE selected is applicable.
Check the Gain value after alignment is within the distance range.
Tests
Perform tests on the installed beam sensor pair.
Commissioning tool
Where required, configure the monitored input and working
indication features.