Commissioning Tool; Vigilon - Commissioning Tool; Nano - Commissioning Tool - Honeywell GENT S4 Data And Installation

Beam sensor & brackets (for vigilon and nano systems)
Hide thumbs Also See for GENT S4:
Table of Contents

Advertisement

S4 Beam Sensor & brackets

Commissioning tool

Vigilon - Commissioning tool

The S4 Beam sensor pairs connected to the loop circuits of a Vigilon panel be configured using
Commissioning tool (³ V1.26). Ensure the 'working indicator' operation and 'monitoring type' are correctly
configured for each beam sensor pair.
Menu selection
Configuration
1a
Beam Config.
1b
The selected device in the beam list
had its settings changed the last time
on the date shown here.
L1 - loop circuit 1
Dev 6 - device number 6
'Beam Tx' - is the device label

Nano - Commissioning tool

The Nano Commissioning tool V1.2 does not allow for 'working indicator' operation and 'monitoring type'
functions.
4188-968 issue 4_Part 2_07-12_S4 mains interface
Icon selection
1
5
Commissioning information
2
Select a beam sensor from the list
3
Check the working indicator box if required.
(The factory default is unchecked,
ie working indication is not given)
4
Select the monitoring type which is
applicable for the 'beam Transmitter' only.
The options include:
£
Unmonitored repeat LED
£
Monitored test input
Monitored test input must be selected for
'beam transmitter' having a Test Keyswitch
connected to its base.
15