Honeywell GENT S4 Data And Installation page 7

Beam sensor & brackets (for vigilon and nano systems)
Hide thumbs Also See for GENT S4:
Table of Contents

Advertisement

S4 Beam Sensor & brackets
"
On first power up of the system having beam sensors a light indication of 'Sensor out of Specification' is
given at each beam sensor, with the left most Red LED on the beam sensor lit.
j
Assuming the beam sensor pair are in rough alignment at the control panel activate the [Autogain]
function on the 'beam receiver' of the beam sensor pair to be commissioned. You will need to know the
device address of the 'beam receiver' and the loop number on which it resides.
Procedure for Vigilon panel (Access level 3)
[Test/Eng]
[UserCode]
Params
[Loop]
1-207
[E]
[C] [Q]
Params
1-8
An 'Auto Gain' is carried out at the 'beam receiver'.
Procedure for Nano panel (Access level 4)
Menu
Engineering
Select
k
Using the options in [Test/Eng] menu put the required beam pair into [Align] mode.
Procedure for Vigilon panel (Access level 3)
[Test/Eng]
[UserCode]
Params
[Device]
1-207
Params
[Loop]
1-207
Params
[E]
[C] [Q]
1-8
The Alignment function is activated.
The alignment function will timeout after 1 hour.
4188-968 issue 4_Part 2_07-12_S4 mains interface
[Loop]
<etc>
Enter the 'beam receiver' device address
Enter the
loop number
on which the 'beam receiver' is installed
Enter the
the 'beam receiver' is installed
Loop
Select
Select
Autogain
[Loop]
<etc>
Enter the '
Beam receiver'
Enter the '
Beam transmitter'
Enter the
loop number
on which the Beam sensor pair are installed
Commissioning information
[AutoGain]
loop number
on which
>
Select
16:15 Mon 16/02/09
Warning! Selecting this option will
initiate the beam autogain procedure.
Enter Beam RX Address [ 1]
Accept
[Align]
device address
device address
Beams
>
Enter the 'beam
receiver' device
address
To scroll the range 1-127
Accept
Quit
3